Specifications
Electrical Specifications
Electrical Specifications
Models
Product Name
SMARTRE 2500
SMARTRE 3000
SMARTRE 5000
SMARTRE 6000
Part Numbers
SRE2500-120-NA
SRE2500-120/240-NA
SRE3000-120-NA
SRE3000-120/240-NA
SRE5000-120/240-NA SRE6000-120/240-NA
Continuous Power Rating
2500 VA
3000 VA
5000 VA
6000 VA
Sell
120 Vac
120 Vac
120 Vac
120 Vac
L-N: 120 Vac
L-L: 240 Vac
L-N: 120 Vac
L-L: 240 Vac
Nominal Output
Voltage
Invert 120
Vac
L-N: 120 Vac
L-L: 240 Vac
120 Vac
L-N: 120 Vac
L-L: 240 Vac
L-N: 120 Vac
L-L: 240 Vac
L-N: 120 Vac
L-L: 240 Vac
Nominal Frequency Output
60 Hz
Peak (1 ms)
70 A @ 120 Vac
70 A @ 120 Vac
35 A @ 240 Vac
70 A @ 120 Vac
70 A @ 120 Vac
35 A @ 240 Vac
70 A @ 120 Vac (per FX)
70 A @ 240 Vac
70 A @ 120 Vac (per FX)
70 A @ 240 Vac
RMS (100
ms)
50 A @ 120 Vac
50 A @ 120 Vac
25 A @ 240 Vac
50 A @ 120 Vac
50 A @ 120 Vac
25 A @ 240 Vac
50 A @ 120 Vac (per FX)
50 A @ 240 Vac
50 A @ 120 Vac (per FX)
50 A @ 240 Vac
Maximum AC
Invert Current
Buy Current
30 A @ 120 Vac
Surge
6000 VA
6000 VA
12000 VA
12,000 VA
5 Seconds
4800 VA
5000 VA
9600 VA
10,000 VA
Maximum
Overload
Capability
30 Minutes
3200 VA
4000 VA
6400 VA
8000 VA
AC Output Current
20.8 A @ 120 Vac
20.8 A @ 120 Vac
10.4 A @ 240 Vac
25 A @ 120 Vac
25 A @ 120 Vac
12.5 A @ 240 Vac
20.8 A @ 120 Vac
(per FX) /
20.8 A @ 240 Vac
20.8 A @ 120 Vac
(per FX) /
10.4 A @ 240 Vac
Sell Current
< 5%
Total
Harmonic
Distortion
Invert
Voltage
2% Typical
AC Inputs
(x2) 60A 120 Vac (Grid/Generator)
(x4) 60 A 120/240 Vac (Grid [x2]/Generator [x2])
Anti-Islanding Protection
UL1741-2005/IEEE1547
Output Waveform
True Sine Wave
Maximum PV Array Wattage
4000 Wdc
STC
4000
Wdc
STC
4000
Wdc
STC
4000
Wdc
STC
8000
Wdc
STC
8000
Wdc
STC
Input Voltage Range
50-150 Vdc V
OC
Maximum Voltage Temperature Correction
Operating Voltage Range
50-145 Vdc Maximum Voltage Temperature Correction
Maximum Open Circuit
Voltage
150 V
OC
including local temperature correction factor per NEC 690.7
Maximum PV Short Circuit
Current
64 A I
SC
per NEC 690.8 per PV input
Ground Fault Protection
(x1) 80 Adc Breaker
(Detection >0.5 A)
(x2) 80 Adc Breakers
(Detection >0.5A)
Electronic Over-current
Protection
yes
Separate PV 64A I
SC
per NEC
690.8 Inputs
1 2
Nominal 48
Vdc
Battery Voltage
Operating
Range
40-60 Vdc
Recommended Minimum
Battery Capacity
100 Amp-hours at 48 Vdc / ~ 4 kWH
200 Amp-hours at 48 Vdc / ~ 8 kWH
AC Source
35 Adc
35 Adc
45 Adc
45 Adc
70 Adc
90 Adc
Maximum
Battery Charge
Rate
DC Source
80 Adc
80 Adc
80 Adc
80 Adc
160 Adc
160 Adc
Содержание SmartRE 2500
Страница 1: ...Installation Manual...
Страница 19: ...Planning 900 0033 01 00 Rev A 17 Dimensions Figure 6 Enclosure Dimensions...
Страница 28: ...Installation 26 900 0033 01 00 Rev A Figure 14 Correct Placement for Vertical Installations...
Страница 29: ...Installation 900 0033 01 00 Rev A 27 Removing the Interior Cover Figure 15 Removing the Interior Cover...
Страница 54: ......
Страница 56: ...Wiring Configurations 54 900 0033 01 00 Rev A This page intentionally left blank...
Страница 64: ...Wiring Configurations 62 900 0033 01 00 Rev A This page intentionally left blank...