background image

Page 29

Page 28

900-0125-

12

-

02 Rev A 

©2017 OutBack Power Technologies.  All Rights Reserved.

MATE3s Settings

AGS 

M-1. 

AGS continued

• Voltage Start

Three starting voltages are available.  These are low-voltage set points

which are linked to times of 24 hours, 2 hours, and 2 minutes.
These times indicate how long the batteries should be left at a particular low voltage before starting

the generator for recharge.

If the battery voltage drops below any of these set points, that timer starts counting down.

If the voltage is above the set point, the timer counts up again.

When any timer reaches zero (0), a start command is sent to the generator.

The timers automatically reset to maximum when AGS stops the generator, or upon an AGS fault.

See page 31 to view these timers.

After a generator runs due to 

Voltage Start

, it will be stopped when the inverter completes the battery 

charging cycle.

24 Hour Start Enable

 — enables (

Y

) or disables (

N

) the 24-hour timer.  

Voltage

 should be set for a mild discharge.

The range varies with battery voltage.

2 Hour Start Enable

 — enables (

Y

) or disables (

N

) the 2-hour timer.  

Voltage

 should be set for a major discharge.

The range varies with battery voltage.

2 Minute Start Enable

 — enables (

Y

) or disables (

N

) the 2-minute timer.  

Voltage

 should be set for a critical battery

discharge and an emergency generator start.  The range varies with battery voltage.

NOTE

:  The 

Quiet Time

 settings overrides the settings and prevents an automatic start.  The exception is

 2 Minute Start

.  

As an emergency set point, it will start the generator regardless of 

Quiet Time

 settings. 

IMPORTANT:  

If 

DC Generator

 is set to 

Y

, the generator will only stop after reaching the DC generator 

parameters shown on page 27.

• Load Start

The generator can start whenever the system AC load exceeds the

Start

 wattage for the programmed 

Delay

 time.  The generator is stopped

when the AC load drops below a 

Stop

 set point for the 

Delay

 time.

Enabled

 — either enables (

Y

) or disables (

N

) the 

Load Start

 function.

Start

 — the load size (

0

 to 

50

 kW) which requires the generator to start following the 

Delay

 time (

1

 to 

240

 minutes).

Stop

 — the lower load setting (

0

 to 

49

 kW) which ends the generator operation following the 

Delay

 time (

1

 to 

240

 minutes).

IMPORTANT:  

 

™

Large, instantaneous loads can still overload the inverter if the generator does not start in time.

 

™

When the generator is running because of 

Load Start

, the inverter will charge the batteries.  However,

it is not programmed to perform a complete charge cycle.  If the generator reaches its 

Stop

 point, the 

charge might not be completed.

State-of-Charge (SOC) Start

Occasionally it is not effective for the generator to start on the basis of

voltage.  AGS can operate the generator based on battery SOC information

from the FLEXnet DC battery monitor (FN-DC).

Enable

 — 

Y

 (Yes) causes the MATE3s to start and stop the generator based on the items below. 

N

 (no) disables

this function.

Start SOC

 — When the FN-DC shows an SOC below this setting (

0

 to 

99

%), the generator starts.  (The SOC value is

displayed on the Home screen.  See the 

MATE3s Overview Guide

.)

Stop SOC

 — When the FN-DC shows that the SOC has exceeded this setting (

0

 to 

100

%), the generator stops.

NOTE

:  In some cases the charger may not easily reach a setting of 100% SOC.  It is recommended to set 

Stop SOC

no higher than 

98

%.

If 

Stop SOC

 is not desirable, AGS can stop the generator by another means.

Enable Full Charge

 — When set to 

Y

 (yes), the MATE3s completes a full charging cycle regardless of 

Stop SOC

.

Interval

 — the days (

1

 to 

30

) before 

Enable Full Charge

 is used.

The MATE3s will perform 

Start SOC

 as normal.  The MATE3s compares the 

Interval

 period against the 

Days Since Parms 

Met

 display.  (See the 

MATE3s Overview Guide

.)  If 

Days Since Parms Met 

is equal or higher, then the generator will run until 

the FLEXnet DC’s charge parameters are met, regardless of the SOC value.  (See page 33 for more information.)  

After the cycle is over, the SOC is automatically reset to 100% when the batteries begin to discharge for one minute.

Setting 

Enable Full Charge

 to 

N

 or setting the 

Interval

 to zero (0) days will disable the function.

Must Run Schedule

This is a period of time when the generator is commanded to run

regardless of other conditions.  This is usually set because large loads are

expected to be present.  

Must Run Schedule 

times can be set individually

for weekdays and weekends.

Enable

 — either enables (

Y

) or disables (

N

) the 

Must Run 

function.

Weekday Start 

— the daily time (

00:00

 to 

23:59

, Monday through Friday) when the generator must start.

Weekday Stop

 — the daily time (

00:00

 to 

23:59

, Monday through Friday) when the generator must stop after 

Weekday Start

.

Weekend Start

 — the daily time (

00:00 

to 

23:59

, Saturday and Sunday) when the generator must start.

Weekend Stop

 — the daily time (

00:00

 to 

23:59

, Saturday and Sunday) when the generator must stop after 

Weekend Start

.

The 

Must Run Schedule

 is disabled when 

Start

 and 

Stop

 are set to the same time, or if 

Enable

 is set to 

N

.

Содержание MATE3s

Страница 1: ...ks may be registered in the United States and other countries Date and Revision August 2017 Revision B Part Number 900 0125 12 02 Rev B A B C D F B A B MATE3s System Display and Controller Programming...

Страница 2: ...such as when to start or stop a generator The MATE3s allows a user to view monitor and establish all the settings and values that occur while the system is running Occasionally components may be adde...

Страница 3: ...Wizard See the Profile Wizard on page 42 for more information Settings Menus This menu accesses additional menus with settings for the system and for individual devices System Settings S apply to over...

Страница 4: ...eyesight vary with each installation The contrast color brightness and backlighting of the LCD can be adjusted to provide the best visibility for a given location Contrast Range is from 1 to 100 from...

Страница 5: ...access has been limited by A Challenge Installer Password C Optional Any combination of characters up to 15 characters maximum This name is displayed on the Home screen Set User Access Level A This m...

Страница 6: ...nly A and B Turns off the charger for an individual inverter and prevents it from responding to global charger commands Input Support FX class only C Enables the Input Support function if present Not...

Страница 7: ...vation The AUX deactivates three minutes after the Enable condition clears and Auxiliary Relay Radian inverters have an additional Auxiliary Relay This is a switched contact with no 12 Vdc output It h...

Страница 8: ...L1 inverter for single phase parallel or split phase multiple inverter systems OB Slave L2 A secondary L2 inverter for split phase multiple inverter systems L2 Phase Master The subphase master inverte...

Страница 9: ...rtain items such as Voltage Limit which are adjustable in other modes Upload Grid Protection These menus can implement any of several GIP files which can be downloaded from the OutBack website The GIP...

Страница 10: ...vated when the GridZero or Grid Tied input modes are selected See page 11 All items described on this page are enabled according to regulatory specifications Grid Support Functions indicates whether t...

Страница 11: ...al features this as an option under RTS Compensation Limited Lower and Upper Battery Voltage Adjust the lowest and highest allowed compensated voltage The Owner s Manual features these as an option un...

Страница 12: ...g Disconnect Disconnect Delay The time after reaching Disconnect before the output is activated Threshold The low voltage setting that activates the output following the Hysteresis Time ON Time The le...

Страница 13: ...er to turn on or off any of three shunts current sensors used by the battery monitor These are designated as shunts A B and C For more information on the use of each shunt see the Owner s Manual for t...

Страница 14: ...f it had previously been manually disabled CAUTION Equipment Damage This function can damage the generator or the batteries if either are not properly maintained Be sure to follow all maintenance requ...

Страница 15: ...of Load Start the inverter will charge the batteries However it is not programmed to perform a complete charge cycle If the generator reaches its Stop point the charge might not be completed State of...

Страница 16: ...ing the exercise period This is mostly applicable to DC generators IMPORTANT Regularly running a generator keeps engine components lubricated expels excess moisture charges the starting battery and he...

Страница 17: ...two columns in the table below are a list of start reasons The remaining columns display the possible reasons for the generator to stop The possible stop reasons are connected to the start reasons Fo...

Страница 18: ...X class inverters use Device Type 2 while FLEXmax charge controllers are Type 3 The FLEXnet DC Battery Monitor is Device Type 4 Device Types not depicted here include FXR class inverters Type 5 and Ra...

Страница 19: ...stem to reconnect to the utility grid Grid Connect Delay 0 to 240 minutes The delay period after reaching Grid Connect before the system reconnects to the utility grid Grid Disconnect xx x VDC inverte...

Страница 20: ...iod is ignored If the battery voltage falls below the inverter s Low Battery Cut Out voltage the inverter will automatically connect to the AC input source regardless of the time of day setting EXAMPL...

Страница 21: ...for more information on this function If the battery voltage exceeds the target the 12V AUX output will open the ROCB This removes the AC source from the grid tied inverter shutting it down This will...

Страница 22: ...ce programming and saving is complete press Exit to return to the Main Menu W 2 Using Existing Profiles If the most recent profile was lost or changed it can be retrieved from an SD card and applied t...

Страница 23: ...battery Capacity in B above See I 6 on page 12 for more information on battery charging Wizard Date Time A Hour Minute Day Month Year Weekday NOTE See S 6 on page 6 for more information on clock setti...

Страница 24: ...y pressing Save will automatically default to Option 2 below 1 Select a name on the list with the control wheel Press the Save soft key N to save the new settings over the selected profile Saving to S...

Страница 25: ...1 0 01 99 4 12 17 81 2 17 9 0 11 72 2 06 98 4 11 17 83 1 67 9 0 12 54 1 55 98 NOTE This header line is included in the download Device Data Logs D Users can create Device Data Logs for the FLEXmax FM...

Страница 26: ...Log is downloaded to an SD card an elg file is created This file can be opened in Notepad or MS Word as a text file Event logs can be used to identify repeated symptoms and other patterns A partial E...

Страница 27: ...these steps to help determine the nature of the fault This may also help resolve the problem See the MATE3s Overview Guide for more information on the EVENTS indicator To investigate event messages 1...

Страница 28: ...g the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between...

Отзывы: