Inverter Settings

Grid and Gen AC Input

Inverter Settings (

I

)

Many of the inverter settings in this section apply to all classes of inverters.  However, some inverters use different 

screens.  In cases where screens are different or product-specific, the title indicates the inverter class. 

I-1

.   

Search

I-2

.   

AC Input and Current Limit

I-3a

Grid

 and 

Gen AC Input Mode and Limits 

(FXR/Radian-class)

I-3b

Grid

 and 

Gen AC Input Voltage Limits

 (FX-class)

I-4

.  

AC Output

I-5

.  

Low Battery

I-6

.  

Battery Charger

I-7

.  

Battery Equalize

I-8

.    

Auxiliary Output / Relay

I-9

.   

 Inverter Stacking

I-10

.  

Power Save Ranking

I-11

.  

Grid-Tie Sell

I-1. Search

This function can minimize inverter power draw when no loads are present. 

Name

 — Adjusts the Search mode sensitivity while searching for loads.

Setting this item to zero will disable 

Search

 mode.

Pulse Length

 — Adjusts the duration of search pulses (in single AC cycles).

Longer pulses will detect loads more quickly.  This consumes more power.

Pulse Spacing

 — Adjusts the time between

search pulses (in single AC cycles).

Shorter spacing will detect loads more

quickly.  This consumes more power.

I-2. AC Input and Current Limit

This menu controls the input current that the inverter can draw.  It has  

independent settings for two AC sources.  It is common for one source to be 

the utility grid and the other is an AC generator.  The settings are labeled  

accordingly.  (It also has an independent setting for the inverter’s charger.)  

NOTE

:  FX-class, FXR-class, and Radian-class inverters interact differently with  

multiple AC sources.  Note also that several items in this menu are also controlled 

in the <

Input Select

>

 

soft key menu.  See the 

MATE3s Overview Guide

.

Adjust these settings to the size of the input circuit breaker or conductor.   

This is for protection.  If combined charging and loads exceed this setting, 

the inverter automatically reduces its charge rate.  (The loads receive   

priority.)  If the loads exceed the limit on their own, the charge reduces to   

zero.  This setting may be assisted by the Input Support function, if present. 
Beyond this point, the input breaker may trip.  This is accompanied by a  

MATE3s event and the warning

 Input Amps > Max

NOTE

:  If multiple parallel inverters are installed with a limited AC source, the combined amperage settings must be less than 

the AC input circuit.  The MATE3s Profile Wizard can perform this calculation.  (See page 45.) 

Input Type

 — (FX-class and FXR-class only; 

A

C

D

) – The inverter has two choices for AC sources: 

Grid

 or 

Gen

.  It cannot use both

at once, but it can be switched between them using an external selector switch.  The user can select between defined parameters for each

source.  (See 

I-3

.  See page 44 for the effects of the Profile Wizard on this setting.)

In FX-class grid-interactive models, this sets the charging format and other parameters.  

Gen

 prevents the inverter from selling power.

Input Priority

 — (Radian-class only; 

B

) – The inverter can be wired to two AC sources: 

Grid

 or 

Gen

.  It can accept either source but

cannot use both at once.  However, it will accept one input as a default selection if both sources are active at the same time.

Grid

 and 

Gen Input AC Limit

 — Adjusts the inverter’s draw to the size of the appropriate input circuit or source.  (See page 45.)

Charger AC Limit

 — Adjusts the draw of the inverter’s charger.  This setting can be limited to avoid accidentally overcharging the

batteries.  It should not exceed the maximum charge rate of the battery bank.  (See page 44.)

Charger Control

 — (FXR-class and Radian-class only; 

A

 and 

B

) – Turns off the charger for an individual inverter and prevents it from

responding to global charger commands.

Input Support — (FX-class only; 

C

) – Enables the Input Support function, if present.  Not all FX-class inverters have this function (

D

).

NOTE

:  

Input Support 

is present in Radian- and FXR-class inverters, but is not selectable.  It only works in 

Support

 mode.  See 

I-3a

.

I-12

.  

Module Control

I-13

 Calibrate

I-14

.  

Grid Interface Protection

I-15

.  

Model Select

I-16

.  

Reset to

           Factory Defaults

NOTE

:  Items 

1-3a

 and 

1-3b

 use the same location in the 

Inverter

 menu, but are used in different models.

I-3a. Grid 

and

 Gen Input Mode and Limits

(FXR-class and Radian-class)

The inverter will not connect to a source unless specific conditions are met.   

 

Each input has a menu to adjust the conditions.  In the Radian, the 

Grid Input 

Mode and Limits 

menu applies to the input labeled 

G

rid

.  

Gen Input Mode  

and Limits 

affects the 

G

en

 input.  In FXR inverters, either menu can apply  

depending on whether the single input is set to accept 

Grid

 or 

Gen

.  See 

I-2

.

When the conditions are met, the inverter will accept the source after the designated delay.

Input Mode

 — Sets this input to one of seven AC input modes (see list).  Each mode has specific advantages

for a particular application.   (See page 44 for the effects of the Profile Wizard on this setting.)

Voltage Limit Lower

 and 

Upper

 — Set the acceptable AC voltage.  If the source is within this range, the inverter

accepts it.  If it exceeds this range, the inverter disconnects itself.  It will return to inverting if that function is active.

Transfer Delay

 — Sets the duration that the input AC voltage or frequency may exceed limits before disconnection.

This may be preceded by a warning and may be followed by a 

Last AC Disconnect

 message.  (See the 

MATE3s

Overview Guide

.)

Connect Delay 

— Sets the delay period before the inverter begins accepting power from the source.  This is intended

to give a generator’s output time to stabilize.  It is not the same as the AGS warmup period (see page 27).

GridZero Mode

DoD Volts

 — Adjusts the lowest allowable battery discharge voltage.  Loads will switch to grid power when this setting is reached.

DoD Amps

 — Adjusts the maximum current (in AC amperes) at which 

GridZero

 mode draws power from the batteries.

Mini Grid Mode

Connect to Grid 

— Adjusts the battery voltage setting that causes the inverter to reconnect to the utility grid in 

Mini Grid

 mode.

(Connect) 

Delay

 — Adjusts the delay period after reaching 

Connect to Grid

 before the inverter reconnects to the grid.

NOTE

:  Certain input modes activate the Grid Support functionality.  Some items may not be available (as in 

A

).  See page 18.

AC Input 

Modes

Generator

Support

Grid Tied

UPS

Backup

Mini Grid

GridZero

I-3b. Grid 

and

 Gen Input Mode and Limit 

(FX-class only)

The inverter will not connect to an AC source unless specific conditions are  

 

met.  When Input Type is set to Grid or Gen in the AC Input and Current   

Limit screen (

I-2

), these menus adjust the limits on acceptable source voltage.  

Frequency is not adjustable.

Lower

 and 

Upper Voltage Limit 

— Set the limits on the acceptable AC voltage.  If the

source is within the appropriate range, the inverter will accept it.  If it exceeds this range,

the inverter will disconnect itself.  It will return to inverting if that function is active.

Transfer Delay

 — Sets the duration that the input AC voltage or frequency may exceed limits before the inverter disconnects itself.  This

may be preceded by a warning and may be followed by a 

Last AC Disconnect message

. (See the 

MATE3s Overview Guide

.)

Connect Delay

 — Sets the delay period before the inverter begins accepting power from the source.  This is intended to give a

generator’s output time to stabilize.  It is not the same as the AGS warmup period (see page 27).

B

A

C

A

D

Содержание MATE3s

Страница 1: ...ks may be registered in the United States and other countries Date and Revision August 2017 Revision B Part Number 900 0125 12 02 Rev B A B C D F B A B MATE3s System Display and Controller Programming...

Страница 2: ...such as when to start or stop a generator The MATE3s allows a user to view monitor and establish all the settings and values that occur while the system is running Occasionally components may be adde...

Страница 3: ...Wizard See the Profile Wizard on page 42 for more information Settings Menus This menu accesses additional menus with settings for the system and for individual devices System Settings S apply to over...

Страница 4: ...eyesight vary with each installation The contrast color brightness and backlighting of the LCD can be adjusted to provide the best visibility for a given location Contrast Range is from 1 to 100 from...

Страница 5: ...access has been limited by A Challenge Installer Password C Optional Any combination of characters up to 15 characters maximum This name is displayed on the Home screen Set User Access Level A This m...

Страница 6: ...nly A and B Turns off the charger for an individual inverter and prevents it from responding to global charger commands Input Support FX class only C Enables the Input Support function if present Not...

Страница 7: ...vation The AUX deactivates three minutes after the Enable condition clears and Auxiliary Relay Radian inverters have an additional Auxiliary Relay This is a switched contact with no 12 Vdc output It h...

Страница 8: ...L1 inverter for single phase parallel or split phase multiple inverter systems OB Slave L2 A secondary L2 inverter for split phase multiple inverter systems L2 Phase Master The subphase master inverte...

Страница 9: ...rtain items such as Voltage Limit which are adjustable in other modes Upload Grid Protection These menus can implement any of several GIP files which can be downloaded from the OutBack website The GIP...

Страница 10: ...vated when the GridZero or Grid Tied input modes are selected See page 11 All items described on this page are enabled according to regulatory specifications Grid Support Functions indicates whether t...

Страница 11: ...al features this as an option under RTS Compensation Limited Lower and Upper Battery Voltage Adjust the lowest and highest allowed compensated voltage The Owner s Manual features these as an option un...

Страница 12: ...g Disconnect Disconnect Delay The time after reaching Disconnect before the output is activated Threshold The low voltage setting that activates the output following the Hysteresis Time ON Time The le...

Страница 13: ...er to turn on or off any of three shunts current sensors used by the battery monitor These are designated as shunts A B and C For more information on the use of each shunt see the Owner s Manual for t...

Страница 14: ...f it had previously been manually disabled CAUTION Equipment Damage This function can damage the generator or the batteries if either are not properly maintained Be sure to follow all maintenance requ...

Страница 15: ...of Load Start the inverter will charge the batteries However it is not programmed to perform a complete charge cycle If the generator reaches its Stop point the charge might not be completed State of...

Страница 16: ...ing the exercise period This is mostly applicable to DC generators IMPORTANT Regularly running a generator keeps engine components lubricated expels excess moisture charges the starting battery and he...

Страница 17: ...two columns in the table below are a list of start reasons The remaining columns display the possible reasons for the generator to stop The possible stop reasons are connected to the start reasons Fo...

Страница 18: ...X class inverters use Device Type 2 while FLEXmax charge controllers are Type 3 The FLEXnet DC Battery Monitor is Device Type 4 Device Types not depicted here include FXR class inverters Type 5 and Ra...

Страница 19: ...stem to reconnect to the utility grid Grid Connect Delay 0 to 240 minutes The delay period after reaching Grid Connect before the system reconnects to the utility grid Grid Disconnect xx x VDC inverte...

Страница 20: ...iod is ignored If the battery voltage falls below the inverter s Low Battery Cut Out voltage the inverter will automatically connect to the AC input source regardless of the time of day setting EXAMPL...

Страница 21: ...for more information on this function If the battery voltage exceeds the target the 12V AUX output will open the ROCB This removes the AC source from the grid tied inverter shutting it down This will...

Страница 22: ...ce programming and saving is complete press Exit to return to the Main Menu W 2 Using Existing Profiles If the most recent profile was lost or changed it can be retrieved from an SD card and applied t...

Страница 23: ...battery Capacity in B above See I 6 on page 12 for more information on battery charging Wizard Date Time A Hour Minute Day Month Year Weekday NOTE See S 6 on page 6 for more information on clock setti...

Страница 24: ...y pressing Save will automatically default to Option 2 below 1 Select a name on the list with the control wheel Press the Save soft key N to save the new settings over the selected profile Saving to S...

Страница 25: ...1 0 01 99 4 12 17 81 2 17 9 0 11 72 2 06 98 4 11 17 83 1 67 9 0 12 54 1 55 98 NOTE This header line is included in the download Device Data Logs D Users can create Device Data Logs for the FLEXmax FM...

Страница 26: ...Log is downloaded to an SD card an elg file is created This file can be opened in Notepad or MS Word as a text file Event logs can be used to identify repeated symptoms and other patterns A partial E...

Страница 27: ...these steps to help determine the nature of the fault This may also help resolve the problem See the MATE3s Overview Guide for more information on the EVENTS indicator To investigate event messages 1...

Страница 28: ...g the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between...

Отзывы: