SYSTEM-40 BTU MEASUREMENT SYSTEM
30240
User Defined Volume Total - Mode 1 - Liters
Input Register
Floating Point Register (2 of 2)
30241
User Defined Volume Total - Mode 1 - ft3
Input Register
Floating Point Register (1 of 2)
30242
User Defined Volume Total - Mode 1 - ft3
Input Register
Floating Point Register (2 of 2)
30243
User Defined Volume Total - Mode 1 - m3
Input Register
Floating Point Register (1 of 2)
30244
User Defined Volume Total - Mode 1 - m3
Input Register
Floating Point Register (2 of 2)
30245
User Defined Volume Total - Mode 2 - Gal
Input Register
Floating Point Register (1 of 2)
30246
User Defined Volume Total - Mode 2 - Gal
Input Register
Floating Point Register (2 of 2)
30247
User Defined Volume Total - Mode 2 - Liters
Input Register
Floating Point Register (1 of 2)
30248
User Defined Volume Total - Mode 2 - Liters
Input Register
Floating Point Register (2 of 2)
30249
User Defined Volume Total - Mode 2 - ft3
Input Register
Floating Point Register (1 of 2)
30250
User Defined Volume Total - Mode 2 - ft3
Input Register
Floating Point Register (2 of 2)
30251
User Defined Volume Total - Mode 2 - m3
Input Register
Floating Point Register (1 of 2)
30252
User Defined Volume Total - Mode 2 - m3
Input Register
Floating Point Register (2 of 2)
30253
Auxiliary Pulse Input Count- Input 1
Input Register
Floating Point Register (1 of 2)
Unitless count. Value is representative
of the total number of pulses received
on input.
30254
Auxiliary Pulse Input Count- Input 1
Input Register
Floating Point Register (2 of 2)
Unitless count. Value is representative
of the total number of pulses received
on input.
30255
Auxiliary Pulse Input Count- Input 2
Input Register
Floating Point Register (1 of 2)
Unitless count. Value is representative
of the total number of pulses received
on input.
30256
Auxiliary Pulse Input Count- Input 2
Input Register
Floating Point Register (2 of 2)
Unitless count. Value is representative
of the total number of pulses received
on input.
30257
Auxiliary Pulse Input Count- Input 3
Input Register
Floating Point Register (1 of 2)
Unitless count. Value is representative
of the total number of pulses received
on input.
30258
Auxiliary Pulse Input Count- Input 3
Input Register
Floating Point Register (2 of 2)
Unitless count. Value is representative
of the total number of pulses received
on input.
30259
Run Hours
Input Register
Floating Point Register (1 of 2)
30260
Run Hours
Input Register
Floating Point Register (2 of 2)
30261
Meter Status
Input Register
Short Integer Register
0 Normal
1 Low Supply Temperature
2 High Supply Temperature
3 Low Return Temperature
4 High Return Temperature
5 Delta T < Minimum
6 High Energy Rate
7 Low Signal Quality
8 Comm Error
9 Low Supply Voltage
10 System Fault
8.1 MODBUS MEMORY MAP (CONTINUED)