SYSTEM-40 BTU MEASUREMENT SYSTEM
SECTION 7.0
BACNET MS/TP
BACnet MS/TP, serial interface connections are connected at terminal block TB4.
Transceiver: 2-wire, half-duplex (1/4 unit load)
BACnet address (MAC address) range: 1 - 127 (Default: 017)
Device Instance: 0 - 4,194,302 (Default: 57017)
Baud rate: 9600, 19200, 38400 or 76800 (Default: 38400)
Termination: 120 ohms or none (Default: none)
Biasing: None
Flow control: None
BACnet Object Type and Number of Objects Implemented Device - 1
Analog Input - 10
Analog Value - 24
Binary Value- 10
Multistate Object - 1
Trend Log Multiple - 1
BACnet Protocol Revision: 10
Device Profile (Annex L): BACnet Application Specific Controller (B-ASC) MS/TP
master (Clause 9), baud rate(s): 9600, 19200, 38400 & 76800
Device Address Binding: No
BBMD support registration by Foreign Devices: No
Character Set Supported: ANSI X3.4
BACnet Interoperability Building Blocks Supported (Annex K):
Data Sharing-ReadProperty-B (DS-RP-B)
Data Sharing - ReadProperty Multiple - B (DS-RPM-B)
Data Sharing-WriteProperty-B (DS-WP-B)
Data Sharing - WriteProperty Multiple - B (DS-WPM-B)
Device Management-Dynamic Device Binding - B (DM-DDB-B)
Device Management-Dynamic Object Binding - B (DM-DOB-B)
Device Management-DeviceCommunicationControl-B (DM-DCC-B)
Device Management-Time Synchronization - B (DM-TS-B)
Device Management - UTC Time Synchronization – B (DM-UTC-B)
Trending - View and Modify Multiple Values - I – B (T-VMMV-I-B)
Standard Object Types Supported:
Device Object
Binary Value Object
Analog Input Object
Multi-State Value
Analog Value Object
Trend Log Multiple
7.1 BACNET OBJECT TYPES
7.2 PROTOCOL
IMPLEMENTATION
STATEMENT