SYSTEM-40 BTU MEASUREMENT SYSTEM
Energy Total
NEXT
BACK
MENU
!
0
kBtu
Volume Total
NEXT
BACK
MENU
0
gallons
Energy Rate
4-20 ma = 0 to 300
NEXT
BACK
MENU
0
kBtu/hr
Volume Rate
NEXT
BACK
MENU
0
gpm
4.3 USER SCREEN
User Screens
Commissioning
NEXT
SEL
!
Main Menu
User screens are read only display pages of the current information and settings
in the meter. Changes to any of these pages can only be made during the
commissioning process. (see section 4.2).
After the meter has been commissioned, verify that the meter is functional
by stepping through the display pages and confirming the flow rate and
temperature data is within expected norms.
Momentarily press
NEXT
or
BACK
to change the display pages, or
MENU
to
get to the troubleshooting menu. See section 6.0 TROUBLESHOOTING for more
details on the alarm messages and their solutions.
4.3.1 Single Mode
Single mode is the energy calculation in either the heating or cooling mode. It is
chosen through commissioning the meter. See 4.2.2.1 METER CONFIGURATION
SETTINGS for more details on how to select the mode status.
Below are the default setup screens for Single Mode. Energy Total, Volume Total,
Energy Rate, and Volume Rate units are factory defaults.
Energy Total
provides the total energy of the system tabulated by the meter.
Volume Total
provides the flow volume total of the system tabulated by the
meter.
Energy Rate
provides a continuous display of the instantaneous energy rate of
the system is tabulated by the meter. Scaling for the 4-20 mA, 0-5V or 0-10 V
analog outputs will also be displayed.
Volume Rate
provides a continuous display of the instantaneous flow rate of the
system tabulated by the meter.