ONICON Incorporated 727-447-6140
Page 24
www.onicon.com
SYSTEM-40 BTU MEASUREMENT SYSTEM
MODBUS address range: 0 – 247 (Default: 017). Press
EDIT
, then
MORE
to select
digits. To continue, press
SAVE
and then
NEXT
.
Baud rate for the MODBUS communications. Options included: 9600, 19200,
38400 or 76800 or 115200. (Default: 9600). Press
EDIT
, then
MORE
to select
digits. To continue, press
SAVE
and then
NEXT
.
Error checking parity for the MODBUS communications. Options include:
None, Odd, or Even (Default: None). Press
EDIT
, then
MORE
to select parity. To
continue, press
SAVE
and then
NEXT
.
Stop bits options include: 1 or 2 (Default: 1). Press
EDIT
, then
MORE
to select
digit. To continue, press
SAVE
and then
NEXT
.
Modbus Address
0-247
NEXT
017
EXIT
EDIT
Baud Rate
NEXT
9600
EXIT
EDIT
Parity
Odd Even None
NEXT
None
EXIT
EDIT
Stop Bits
1 2
NEXT
1
EXIT
EDIT
4.2.1.2 Communication Settings – MODBUS
To select MODBUS, press
EDIT
, then
MORE
. To continue, press
SAVE
and then
NEXT
.
Protocol
NEXT
Modbus
EXIT
EDIT