5-6
Section
Clock Function
229
5-6
Clock Function
The NT620S/620C has a clock function for setting the date and time.
This section explains how to set the date and time, and how to notify the date and
time to the PC.
Reference
When the voltage of the battery in the NT620S/620C becomes low, the clock
function will not operate correctly when the power is switched off.
5-6-1 About the Clock Function
The clock function uses the numeral memory tables numbered 247 through 255:
these memory tables are used exclusively for clock data.
As shown in the table below, numbers 247 through 253 are for display and read-
ing only, and numbers 254 and 255 are for time setting. Numbers 247 through
253 store clock data which is updated by the internal clock of the NT620S/620C.
This data cannot be rewritten by the PC.
Function
Numeral
memory table
Bit
Information
Value
Remarks
Display/reading
l
247
Second
00 to 59
y
g
only
248
Minute
00 to 59
249
Hour
00 to 23
24-hour system
250
Date
01 to 31
251
Month
01 to 12
252
Year
00 to 99
Last 2 digits of year
253
Day of week
00 to 06
See below
Setting only
254
0 to 7
8 to 15
16 to 23
24 to 31
Second
Minute
Hour
Date
00 to 59
00 to 59
00 to 23
01 to 31
24-hour system
255
0 to 7
8 to 15
16 to 23
24 to 31
Month
Year
Day of week
Vacant
01 to 12
00 to 99
00 to 06
Always 00
Last 2 digits of year
See below
* The numerical values that correspond to the days of the week are as follows:
Day of
week
Sun
Mon
Tue
Wed
Thu
Fri
Sat
Value
00
01
02
03
04
05
06
Setting example: April 27, 1995, 14:53:30
254
255
27
14
53
30
00
04
95
04
5-6-2 Date and Time Display
In order to display the date or time, an area in which the contents of numeral
memory tables 247 through 253 can be displayed must be set during screen cre-
ation with the support tool.
Numeral memory tables 247 through 253 store clock data which is updated by
the internal clock of the NT620S/620C. This data cannot be rewritten by the PC.
Содержание NT620C
Страница 1: ...Cat No V033 E1 5 Programmable Terminals NT620S 620C OPERATION MANUAL...
Страница 2: ...NT620S 620C Programmable Terminals Operation Manual Revised April 2001...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 326: ...Appendix K Option List 325 Battery 3G2A9 BAT08 This is a lithium battery used for memory backup...
Страница 328: ......
Страница 329: ......