2-5
Section
Connection to a PC by the Host Link
35
Connecting to C Series CPM1
The CPM1 is connected via an RS-232C adapter (type CPM1-CIF01).
Procure an RS-232C 9-pin type connection cable for the connection.
When a connector cable of 5 m or longer is required
When a connector cable of 5 m or longer is required, please make the cable.
However, note that the maximum transmission distance is 15 m.
To make a connector cable, refer to Appendix G “Method for Making the Cable for
Connection to the PC” (page 301).
When Long-Distance Transmission is Required
When transmission over a distance exceeding the RS-232C specification is re-
quired, it can be achieved by using an RS-232C/RS-422A converter unit (type
NT-AL001) to switch to RS-422A communication (RS-485 communication can-
not be used).
For details, refer to Appendix I “Connecting to an RS-232C/RS-422 Converter
Unit” (page 315 of the appendix).
2-5-3 PC Switch Settings
When the NT620S/620C and PC are connected to each other, set the conditions
at the PC host link unit or the CPU as given in the table below.
The following is a general description of switch settings.
Refer to the manual for respective units for the details of the switch settings.
Item
Switch Setting
I/O port
RS-232C
Baud rate
Set the same baud rate as the NT620S. (*1)
Transfer code
ASCII 7 data bits, 2 stop bits
Parity
Even
1-to-1/1-to-N
1-to-N (*2)
Instruction level
Level 1, 2, 3
Unit #
00
Note *1.
Set the host link baud rate at 9600 bps or 19200 bps with the memory switch
for “host link baud rate”. For the details, refer to “Selecting the Host Link
Communication Speed” (page 73).
*2.
The 1-to-N setting enables BCC (Block Check Character). The 1-to-N con-
nection cannot be used to connect the NT620S/620C to one host link unit.
Correct use
When using CVM1/CV series, always set “CPU execution processing (execu-
tion control 2)” in the PC system settings to “simultaneous processing”.
Содержание NT620C
Страница 1: ...Cat No V033 E1 5 Programmable Terminals NT620S 620C OPERATION MANUAL...
Страница 2: ...NT620S 620C Programmable Terminals Operation Manual Revised April 2001...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 326: ...Appendix K Option List 325 Battery 3G2A9 BAT08 This is a lithium battery used for memory backup...
Страница 328: ......
Страница 329: ......