75
F3SG-4RA-25-02TS
User’s Manual
Chapter
4
Wiring
Wiring/Installation
E
If the length of the F39-JD
A Single-Ended Cable is insufficient, use 1 or more F39-JD
B Double-
Ended Cables to extend the length, as required. The total cable extension length of the power cable
must be 100 m max.
<Connection example>
4-5-3-4. Cascading Cable
Cascading Cable for Emitter (F39-JGR2WTS-L, sold separately)
Cascading Cable for Receiver (F39-JGR2WTS-D, sold separately)
Set model name
Emitter cable (Gray)
Receiver cable (Black)
L (m)
F39-JGR2WTS
F39-JGR2WTS-L
F39-JGR2WTS-D
0.2
Emitter
Receiver
Cable is gray
Model F39-JD
B-L(Gray)
Model F39-JD
A-L(Gray)
Double-Ended Cable
Model F39-JD
B
Single-Ended Cable
Model F39-JD
A
Cable is black
Model F39-JD
B-D(Black)
Model F39-JD
A-D(Black)
200
Φ 14.9
40.7
Φ 6
23.4
10
Insulated vinyl round cable dia. 6 mm, 5-wire
(Cross section of conductor: 0.15 mm
2
(AWG26) / Insulator diameter: dia. 1 mm)
Connector
M12 IP67 connector
24.2
[Unit: mm]
M2.5 screw
200
Φ 14.9
40.7
Φ 6
23.4
10
Insulated vinyl round cable dia. 6 mm, 8-wire
(Cross section of conductor: 0.15 mm
2
(AWG26) / Insulator diameter: dia. 1 mm)
Connector
M12 IP67 connector
24.2
M2.5 screw
[Unit: mm]
Содержание F3SG-R Series
Страница 19: ...xvii F3SG 4RA 25 02TS User s Manual Introduction E 7 4 Revision History 107...
Страница 20: ...xviii Introduction F3SG 4RA 25 02TS User s Manual...
Страница 52: ...32 Chapter 3 End Cap F3SG 4RA 25 02TS User s Manual Setting with Rotary Switch and End Cap...
Страница 106: ...86 Chapter 5 Connectable Safety Control Units F3SG 4RA 25 02TS User s Manual Input Output Circuit and Applications...
Страница 112: ...92 Chapter 6 Maintenance Checklists F3SG 4RA 25 02TS User s Manual Checklists...