201
5. Set the scaling value teach command code C510 for the X2 value. The input
word will be set to the response C510.
CHG
SHIFT
C
2
C
F
5
B
1
A
0
WRITE
c100 c001
C510 C510
6. Set 0000 to the output word. When 03E8 is set to the input word, converted
from 1000 (i.e., the scaled conversion data of the largest object measured
with the Unit), the teaching for the X2 value has been correctly executed.
CHG
A
0
A
0
A
0
A
0
WRITE
c100 c001
0000 03E8
1000
To check the adjusted values, execute the scaling value read command with the
command code C600 or C610. The X1 value will read 0403 and the X2 value will
read 1993.
6-2
Set Value Teaching
The set value teach command can be used for the Unit only when the timing hold
in operation mode A is set to normal.
It is possible to use appropriate sample objects and adjust the set scaling values
by executing set value teaching with the set value teach command as follows.
•
LL Set Value:
C800
•
L Set Value:
C810
•
H Set Value:
C820
•
HH Set Value: C830
Setting Example
In this example, the timing hold is set to normal, and the L or H set value is ad-
justed using the teach function. The L set value is used for the smallest object of
all the objects measured by the Unit and the H set value is used for the largest
object of all the objects. The Unit is set to measurement mode so that the Unit will
display the results of the operation.
Operation
For the Smallest Object
1, 2, 3...
1. Adjust the L value with the smallest object using the set value teaching func-
tion. The input word reads 0100, which is the scaled conversion data of the
smallest object measured with the Unit, and the output word reads 0000.
c100 c001
0000 0100
Output word Input word
2. Input the set value teach command code C810 for the L value. To input the
letter C with the Programming Console, press the Shift and 2 Keys. The in-
put word will be set to the response C810.
CHG
SHIFT
C
2
C
8
B
1
A
0
WRITE
c100 c001
C810 C810
3. Set 0000 to the output word. 0100 will be set to the input word.
CHG
A
0
A
0
A
0
A
0
WRITE
c100 c001
0000 0100
Set Value Teaching
Section 6-2
Содержание CQM1H - 08-2005
Страница 1: ...Cat No W238 E1 8 Dedicated I O Units CQM1H CQM1 series OPERATION MANUAL SYSMAC ...
Страница 2: ......
Страница 3: ...CQM1H CQM1Series Dedicated I O Units Operation Manual Revised August 2000 ...
Страница 4: ......
Страница 6: ......
Страница 12: ......
Страница 21: ...1 PART I B7A Interface Unit CQM1 B7A02 CQM1 B7A03 CQM1 B7A12 CQM1 B7A13 CQM1 B7A21 ...
Страница 22: ......
Страница 42: ......
Страница 45: ...25 PART II G730 Interface Unit CQM1 G7M21 CQM1 G7N01 CQM1 G7N11 ...
Страница 46: ......
Страница 62: ......
Страница 72: ......
Страница 74: ...Appendix A Specifications 54 Dimensions Common for Master and Expansion Master Unit mm ...
Страница 78: ......
Страница 79: ...59 PART III I O Link Unit CQM1 LK501 ...
Страница 80: ......
Страница 88: ......
Страница 92: ......
Страница 93: ...73 PART IV Analog Input Unit and Analog Power Supply Units CQM1 AD041 CQM1 IPS01 CQM1 IPS02 ...
Страница 94: ......
Страница 118: ......
Страница 120: ......
Страница 121: ...101 PART V Analog Output Unit and Analog Power Supply Units CQM1 DA021 CQM1 IPS01 CQM1 IPS02 ...
Страница 122: ......
Страница 126: ......
Страница 140: ......
Страница 142: ......
Страница 144: ......
Страница 156: ......
Страница 172: ......
Страница 186: ......
Страница 187: ...167 PART VII Linear Sensor Interface Units CQM1 LSE01 CQM1 LSE02 ...
Страница 188: ......
Страница 192: ......
Страница 204: ......
Страница 218: ......
Страница 238: ......
Страница 242: ......
Страница 246: ......
Страница 248: ......
Страница 250: ......