Connections to B7A Link Terminals
3-1-1 Recommended Cables
The B7A Interface Unit can be connected to the input and output B7A Link Termi-
nals using the following cables.
Standard Transmission Delay-time Type
Cabtire Cable
Use a VCTF 0.75 x 3 C cabtire cable (100 m max.) if a power supply is shared
and a VCTF 0.75 x 2 C cabtire cable (500 m max.) if power is supplied indepen-
dently.
Rapid Transmission Delay-time Type
Shielded Cable
Use a 0.75 x 3 C shielded cable (50 m max.) if a power supply is shared and a
0.75 x 2 C shielded cable (100 m max.) if power is supplied independently.
Caution
If shielded cable is not used for the high-speed transmission delay-time Link Ter-
minal, the transmission distance is not to exceed 10 m regardless of whether
power supply is shared or wired separately.
3-1-2 Connecting Terminals
Connect the input and output B7A Link Terminals to the B7A Interface Unit via
the following terminals using crimp-style terminals used for CQM1H/CQM1 I/O
Units.
CQM1-B7A21
Unused
Connect to the SIG terminal of
the output B7A Link terminal.
Connect to the negative power supply ter-
minal of the output B7A Link Terminal.
Connect to the SIG terminal of
the input B7A Link Terminal.
Connect to the negative power supply ter-
minal of the input B7A Link Terminal.
A
0
A
1
A
2
A
3
B
0
B
1
B
2
B
3
Word m
Word n
CQM1-B7A13
Unused
Connect to the SIG terminal of
the input B7A Link terminal.
Connect to the negative power supply ter-
minal of the input B7A Link Terminal.
Connect to the SIG terminal of
the input B7A Link Terminal.
Connect to the negative power supply ter-
minal of the input B7A Link Terminal.
A
0
A
1
A
2
A
3
B
0
B
1
B
2
B
3
Word n
Word n + 1
Connections to B7A Link Terminals
Section 3-1
Содержание CQM1H - 08-2005
Страница 1: ...Cat No W238 E1 8 Dedicated I O Units CQM1H CQM1 series OPERATION MANUAL SYSMAC ...
Страница 2: ......
Страница 3: ...CQM1H CQM1Series Dedicated I O Units Operation Manual Revised August 2000 ...
Страница 4: ......
Страница 6: ......
Страница 12: ......
Страница 21: ...1 PART I B7A Interface Unit CQM1 B7A02 CQM1 B7A03 CQM1 B7A12 CQM1 B7A13 CQM1 B7A21 ...
Страница 22: ......
Страница 42: ......
Страница 45: ...25 PART II G730 Interface Unit CQM1 G7M21 CQM1 G7N01 CQM1 G7N11 ...
Страница 46: ......
Страница 62: ......
Страница 72: ......
Страница 74: ...Appendix A Specifications 54 Dimensions Common for Master and Expansion Master Unit mm ...
Страница 78: ......
Страница 79: ...59 PART III I O Link Unit CQM1 LK501 ...
Страница 80: ......
Страница 88: ......
Страница 92: ......
Страница 93: ...73 PART IV Analog Input Unit and Analog Power Supply Units CQM1 AD041 CQM1 IPS01 CQM1 IPS02 ...
Страница 94: ......
Страница 118: ......
Страница 120: ......
Страница 121: ...101 PART V Analog Output Unit and Analog Power Supply Units CQM1 DA021 CQM1 IPS01 CQM1 IPS02 ...
Страница 122: ......
Страница 126: ......
Страница 140: ......
Страница 142: ......
Страница 144: ......
Страница 156: ......
Страница 172: ......
Страница 186: ......
Страница 187: ...167 PART VII Linear Sensor Interface Units CQM1 LSE01 CQM1 LSE02 ...
Страница 188: ......
Страница 192: ......
Страница 204: ......
Страница 218: ......
Страница 238: ......
Страница 242: ......
Страница 246: ......
Страница 248: ......
Страница 250: ......