81
DIP Switch Function
The DIP switch is used to decide the operating method of the Analog Input Unit.
1
3 4 5 6 7 8
2
9 10
Factory setting
ON
OFF
The following tables provides DIP switch settings for Analog Input Unit opera-
tion.
Input Range Settings (Pins 1 to 8)
Input range settings can be made for all inputs.
Input setting
Input range
Input 1
Input 2
Input 2
Input 4
Pin 1: ON
Pin 2: ON
Pin 3: ON
Pin 4: ON
Pin 5: ON
Pin 6: ON
Pin 7: ON
Pin 8: ON
–10 to 10 V
Pin 1: OFF
Pin 2: ON
Pin 3: OFF
Pin 4: ON
Pin 5: OFF
Pin 6: ON
Pin 7: OFF
Pin 8: ON
0 to 10 V
Pin 1: ON
Pin 2: OFF
Pin 3: ON
Pin 4: OFF
Pin 5: ON
Pin 6: OFF
Pin 7: ON
Pin 8: OFF
4 to 20 mA at 1 to 5 V
Pin 1: OFF
Pin 2: OFF
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: OFF
Pin 7: OFF
Pin 8: OFF
Conversion is prohibited
The Analog Input Unit will occupy four words (64 points) when pin 9 is set to ON.
The Analog Input Unit will occupy two words (32 points) when pin 9 is set to OFF.
Set pin 10 to ON to use the average processing function of the Analog Input Unit.
Set pin 10 to OFF if the average processing function is not used.
Caution
All pins must be set before mounting the Analog Input Unit to the CQM1H/
CQM1.
An error will result if pins 1 to 8 are all set to OFF (i.e., if all input conversion is
prohibited).
When pin 9 is set to OFF so that the Analog Input Unit will occupy two words, be
sure to set pins 5 to 8 to OFF.
Do not touch any internal components other than the DIP switch.
The time required for the Analog Input Unit to convert data will not be shortened
even if some inputs are prohibited or if pin 9 is set to OFF so that the Analog Input
Unit will occupy two words.
Word Settings (Pin 9)
Average Processing
Function (Pin 10)
Nomenclature
Section 2-1
Содержание CQM1H - 08-2005
Страница 1: ...Cat No W238 E1 8 Dedicated I O Units CQM1H CQM1 series OPERATION MANUAL SYSMAC ...
Страница 2: ......
Страница 3: ...CQM1H CQM1Series Dedicated I O Units Operation Manual Revised August 2000 ...
Страница 4: ......
Страница 6: ......
Страница 12: ......
Страница 21: ...1 PART I B7A Interface Unit CQM1 B7A02 CQM1 B7A03 CQM1 B7A12 CQM1 B7A13 CQM1 B7A21 ...
Страница 22: ......
Страница 42: ......
Страница 45: ...25 PART II G730 Interface Unit CQM1 G7M21 CQM1 G7N01 CQM1 G7N11 ...
Страница 46: ......
Страница 62: ......
Страница 72: ......
Страница 74: ...Appendix A Specifications 54 Dimensions Common for Master and Expansion Master Unit mm ...
Страница 78: ......
Страница 79: ...59 PART III I O Link Unit CQM1 LK501 ...
Страница 80: ......
Страница 88: ......
Страница 92: ......
Страница 93: ...73 PART IV Analog Input Unit and Analog Power Supply Units CQM1 AD041 CQM1 IPS01 CQM1 IPS02 ...
Страница 94: ......
Страница 118: ......
Страница 120: ......
Страница 121: ...101 PART V Analog Output Unit and Analog Power Supply Units CQM1 DA021 CQM1 IPS01 CQM1 IPS02 ...
Страница 122: ......
Страница 126: ......
Страница 140: ......
Страница 142: ......
Страница 144: ......
Страница 156: ......
Страница 172: ......
Страница 186: ......
Страница 187: ...167 PART VII Linear Sensor Interface Units CQM1 LSE01 CQM1 LSE02 ...
Страница 188: ......
Страница 192: ......
Страница 204: ......
Страница 218: ......
Страница 238: ......
Страница 242: ......
Страница 246: ......
Страница 248: ......
Страница 250: ......