216
Response
If the correct command code or parameter is set to the output word, the same
command code or parameter will be set to the input word.
If the wrong command code or parameter is set to the output word, one of the
following error codes will be set to the input word.
E000: This error code will be set to the input word if a nonexisting command code
is used.
E001: This error code will be set to the input word if the parameter is not within
the range covered by the Unit.
7-3-12 Hysteresis Read
This command is used to read the hysteresis.
Command
Command Code
Parameter
Parameters are not used with this command.
Response
If the correct command code or parameter is set to the output word, the same
command code or parameter will be set to the input word.
Range: 0001 to 0999
Default value: 0001
If the wrong command code or parameter is set to the output word, one of the
following error codes will be set to the input word.
E000: This error code will be set to the input word if a nonexisting command code
is used.
7-3-13 Present Value Read
This command can be used only when the timing hold in operation mode A is set
to normal.
This command is used to read the present measured value after scaling.
Command
Command Code
Parameter
Parameters are not used with this command.
Response
If the correct command code or parameter is set to the output word, the present
conversion data will be set to the input word.
Sign
0: Positive
F: Negative
Value
Range: 0 to 9999
Commands and Responses
Section 7-3
Содержание CQM1H - 08-2005
Страница 1: ...Cat No W238 E1 8 Dedicated I O Units CQM1H CQM1 series OPERATION MANUAL SYSMAC ...
Страница 2: ......
Страница 3: ...CQM1H CQM1Series Dedicated I O Units Operation Manual Revised August 2000 ...
Страница 4: ......
Страница 6: ......
Страница 12: ......
Страница 21: ...1 PART I B7A Interface Unit CQM1 B7A02 CQM1 B7A03 CQM1 B7A12 CQM1 B7A13 CQM1 B7A21 ...
Страница 22: ......
Страница 42: ......
Страница 45: ...25 PART II G730 Interface Unit CQM1 G7M21 CQM1 G7N01 CQM1 G7N11 ...
Страница 46: ......
Страница 62: ......
Страница 72: ......
Страница 74: ...Appendix A Specifications 54 Dimensions Common for Master and Expansion Master Unit mm ...
Страница 78: ......
Страница 79: ...59 PART III I O Link Unit CQM1 LK501 ...
Страница 80: ......
Страница 88: ......
Страница 92: ......
Страница 93: ...73 PART IV Analog Input Unit and Analog Power Supply Units CQM1 AD041 CQM1 IPS01 CQM1 IPS02 ...
Страница 94: ......
Страница 118: ......
Страница 120: ......
Страница 121: ...101 PART V Analog Output Unit and Analog Power Supply Units CQM1 DA021 CQM1 IPS01 CQM1 IPS02 ...
Страница 122: ......
Страница 126: ......
Страница 140: ......
Страница 142: ......
Страница 144: ......
Страница 156: ......
Страница 172: ......
Страница 186: ......
Страница 187: ...167 PART VII Linear Sensor Interface Units CQM1 LSE01 CQM1 LSE02 ...
Страница 188: ......
Страница 192: ......
Страница 204: ......
Страница 218: ......
Страница 238: ......
Страница 242: ......
Страница 246: ......
Страница 248: ......
Страница 250: ......