235
2-2
Specifications
General Specifications
The general specifications of the CQM1-TC20
j
/TC30
j
conform to those of the
CQM1H/CQM1 Series.
Performance Specifications
Item
Specification
Units for thermocouples
(CQM1-TC20
j
)
Units for platinum resistance
thermometers (CQM1-TC30
j
)
Sensor type (See previous page for
temperature ranges.)
K, J, T, L, R, S, B
Pt100, JPt100
Number of control loops
2 loops or 4 loops (2-loop model has heater burnout alarm)
Control output
NPN or PNP output with short-circuit protection
Power supply voltage: 24 VDC
+10%
/
–15%
Maximum switching capacity: 100 mA per output
Leakage current: 0.1 mA max.
Residual voltage: 0.8 V max.
Control mode
ON/OFF control, advanced PID control (2 degrees of freedom), or manual
operation
Setting and display accuracy
°
C Ranges
(Process value
±
0.3% or
±
1
°
C,
whichever is larger)
±
1 digit max.
°
F Ranges
(Process value
±
0.3% or
±
2
°
F,
whichever is larger)
±
1 digit max. (See
note 1.)
The accuracy is given when the cold
junction compensator on the terminal
block is used. Always use the cold
junction compensator on the terminal
block. (See note 2.)
0.1
°
C Ranges
(Process value
±
0.3% or
±
0.8
°
C,
whichever is larger)
±
1 digit max.
0.1
°
F Ranges
(Process value
±
0.3% or
±
1.6
°
F,
whichever is larger)
±
1 digit max. (See
note 1.)
0.01
°
C Ranges
(Process value
±
0.3% or
±
0.5
°
C,
whichever is larger)
±
1 digit max.
Hysteresis adjustment
0.1 to 999.9
°
C/
°
F (0.1
°
C/
°
F unit)
Proportional band
0.1 to 999.9
°
C/
°
F (0.1
°
C/
°
F unit)
Derivative time
0 to 3,999 s (1 s unit)
Integral time
0 to 3,999 s (1 s unit)
Manual manipulated variable
0.0 to 100.0% (0.1% unit)
Control period
1 to 99 s (1 s unit)
Input shift value
–99.9 to 999.9
°
C/
°
F (0.1
°
C/
°
F unit)
0.1
°
C Ranges
–99.9 to 999.9
°
C/
°
F (0.1
°
C/
°
F unit)
0.01
°
C Ranges
–9.99 to 99.99
°
C/
°
F (0.01
°
C/
°
F unit)
Sampling period
0.5 s
Output refresh period
0.5 s
Current consumption
190 mA max. at 5 VDC
Weight
200 g max.
Dimensions
32 x 110 x 107 mm (W x H x D)
Note
1. The accuracy of K and J thermocouples at or below –100
°
C
is
±
2
°
C
±
1 digit
max., and the accuracy of R and S thermocouples at or below 200
°
C
is
±
3
°
C
±
1 digit max. The accuracy of B thermocouples at or below 400
°
C is not
specified.
2. When returning a Unit for repairs, always include the terminal block (or the
cold junction compensator).
Specifications
Section 2-2
Содержание CQM1H - 08-2005
Страница 1: ...Cat No W238 E1 8 Dedicated I O Units CQM1H CQM1 series OPERATION MANUAL SYSMAC ...
Страница 2: ......
Страница 3: ...CQM1H CQM1Series Dedicated I O Units Operation Manual Revised August 2000 ...
Страница 4: ......
Страница 6: ......
Страница 12: ......
Страница 21: ...1 PART I B7A Interface Unit CQM1 B7A02 CQM1 B7A03 CQM1 B7A12 CQM1 B7A13 CQM1 B7A21 ...
Страница 22: ......
Страница 42: ......
Страница 45: ...25 PART II G730 Interface Unit CQM1 G7M21 CQM1 G7N01 CQM1 G7N11 ...
Страница 46: ......
Страница 62: ......
Страница 72: ......
Страница 74: ...Appendix A Specifications 54 Dimensions Common for Master and Expansion Master Unit mm ...
Страница 78: ......
Страница 79: ...59 PART III I O Link Unit CQM1 LK501 ...
Страница 80: ......
Страница 88: ......
Страница 92: ......
Страница 93: ...73 PART IV Analog Input Unit and Analog Power Supply Units CQM1 AD041 CQM1 IPS01 CQM1 IPS02 ...
Страница 94: ......
Страница 118: ......
Страница 120: ......
Страница 121: ...101 PART V Analog Output Unit and Analog Power Supply Units CQM1 DA021 CQM1 IPS01 CQM1 IPS02 ...
Страница 122: ......
Страница 126: ......
Страница 140: ......
Страница 142: ......
Страница 144: ......
Страница 156: ......
Страница 172: ......
Страница 186: ......
Страница 187: ...167 PART VII Linear Sensor Interface Units CQM1 LSE01 CQM1 LSE02 ...
Страница 188: ......
Страница 192: ......
Страница 204: ......
Страница 218: ......
Страница 238: ......
Страница 242: ......
Страница 246: ......
Страница 248: ......
Страница 250: ......