191
Command
Each operation mode set command consists of a command code and parame-
ter. The following command codes are used for the operation mode A and opera-
tion mode B set commands.
•
Operation Mode A: C000
•
Operation Mode B: C200
Refer to pages 208 to 211 for the details of the parameters used for the Unit.
Setting Example
In this example, the following operation modes are selected for the Unit.
•
Data Input:
Comparison mode
•
Timing Hold Mode:
Normal
•
Input Type:
4 to 20 mA
•
Monitor Output:
Scaled conversion data monitor mode
•
Input Sampling Speed:
Fast
•
No. of Averaging Process Times: 1
•
Zero Shift Value Storage Area: RAM
In this example, the initial parameters have been set. Described below is the
method of changing the data input and input type using the operation mode A set
command.
Operation
1, 2, 3...
1. The input word reads 1254, which is the present scaled conversion data,
and the output word reads 0000.
c100 c001
0000 1254
Output word
Input word
2. Set the command code C1000 to the output word to in order to set the opera-
tion mode A. To input the letter C with the Programming Console, press the
Shift and 2 Keys.
The input word will be set to the response C000.
CHG
SHIFT
C
2
C
A
0
A
0
A
0
WRITE
c100 c001
C000 C000
3. Set 2040 to the output word. The Unit will be in comparison mode and the
available input range will be from 4 to 20 mA. All the other modes will remain
unchanged.
CHG
C
2
A
0
E
4
A
0
WRITE
c100 c001
2040 2040
4. When the Unit correctly receives the command, the input word will be set to
2040.
5. Reset 0000 to the output word.
6. The Comparison Result Flags of the input word is turned ON or OFF. In this
example, the input word is set to 0004 (PASS).
CHG
A
0
A
0
A
0
A
0
WRITE
c100 c001
0000 0004
Operation Mode
Section 5-3
Содержание CQM1H - 08-2005
Страница 1: ...Cat No W238 E1 8 Dedicated I O Units CQM1H CQM1 series OPERATION MANUAL SYSMAC ...
Страница 2: ......
Страница 3: ...CQM1H CQM1Series Dedicated I O Units Operation Manual Revised August 2000 ...
Страница 4: ......
Страница 6: ......
Страница 12: ......
Страница 21: ...1 PART I B7A Interface Unit CQM1 B7A02 CQM1 B7A03 CQM1 B7A12 CQM1 B7A13 CQM1 B7A21 ...
Страница 22: ......
Страница 42: ......
Страница 45: ...25 PART II G730 Interface Unit CQM1 G7M21 CQM1 G7N01 CQM1 G7N11 ...
Страница 46: ......
Страница 62: ......
Страница 72: ......
Страница 74: ...Appendix A Specifications 54 Dimensions Common for Master and Expansion Master Unit mm ...
Страница 78: ......
Страница 79: ...59 PART III I O Link Unit CQM1 LK501 ...
Страница 80: ......
Страница 88: ......
Страница 92: ......
Страница 93: ...73 PART IV Analog Input Unit and Analog Power Supply Units CQM1 AD041 CQM1 IPS01 CQM1 IPS02 ...
Страница 94: ......
Страница 118: ......
Страница 120: ......
Страница 121: ...101 PART V Analog Output Unit and Analog Power Supply Units CQM1 DA021 CQM1 IPS01 CQM1 IPS02 ...
Страница 122: ......
Страница 126: ......
Страница 140: ......
Страница 142: ......
Страница 144: ......
Страница 156: ......
Страница 172: ......
Страница 186: ......
Страница 187: ...167 PART VII Linear Sensor Interface Units CQM1 LSE01 CQM1 LSE02 ...
Страница 188: ......
Страница 192: ......
Страница 204: ......
Страница 218: ......
Страница 238: ......
Страница 242: ......
Страница 246: ......
Страница 248: ......
Страница 250: ......