40
3-1
Transmission Cables
Connect wiring in series from the Master, with positive terminals connected to-
gether and negative terminals connected together.
Set the last connected Slave as the terminator. Do not set an intermediate Slave
as a terminator.
Total cable length per system: 200 m max.
The size of terminal screw differs for the Master and Slave. Consider the size of
the terminal screws when using solderless terminals.
Master terminal: M3 (optimum tightening torque: 0.5 N
S
m); Slave terminal:
M3.5 (optimum tightening torque: 0.8 N
S
m)
Locate transmission cables away from power cables and high-voltage cables to
eliminate the effects of noise.
Recommended Cables
The G730 Interface Unit can be connected to the G730 Remote Terminal using
the following cable.
Cable: VCTF 0.75 x 2C
Master to Slave Connection
The connection method of a Master to Slaves is shown in the diagram below.
G730 Interface Unit
Master
G730 Remote Terminal
Slave
+
–
+
–
+
–
G730 Remote Terminal
Slave
Terminal screws: M3
(Optimum tightening torque: 0.5 N
S
m)
Terminal screws: M3.5
(Optimum tightening torque: 0.8 N
S
m)
Set as terminator.
The connection method of a Master and Expansion Master to Slaves is shown in
the following diagram.
Connect wiring of each system in series from Master, Expansion Master to Slave
with positive terminals connected together and negative terminals connected to-
gether.
Expansion Master terminals B0 to B2 and B1 to B3 are shorted internally. They
can be used in any combination.
Set the last connected Slave as the terminator. Do not set an intermediate Slave
as a terminator.
Total cable length per system: 200 m max.
The size of terminal screw differs for the Master/Expansion Master and Slave.
Consider the size of the terminal screws when using crimped terminals.
Master/Expansion Master terminal: M3; Slave terminal: M3.5
Master and Expansion
Master to Slave Connection
Transmission Cables
Section 3-1
Содержание CQM1H - 08-2005
Страница 1: ...Cat No W238 E1 8 Dedicated I O Units CQM1H CQM1 series OPERATION MANUAL SYSMAC ...
Страница 2: ......
Страница 3: ...CQM1H CQM1Series Dedicated I O Units Operation Manual Revised August 2000 ...
Страница 4: ......
Страница 6: ......
Страница 12: ......
Страница 21: ...1 PART I B7A Interface Unit CQM1 B7A02 CQM1 B7A03 CQM1 B7A12 CQM1 B7A13 CQM1 B7A21 ...
Страница 22: ......
Страница 42: ......
Страница 45: ...25 PART II G730 Interface Unit CQM1 G7M21 CQM1 G7N01 CQM1 G7N11 ...
Страница 46: ......
Страница 62: ......
Страница 72: ......
Страница 74: ...Appendix A Specifications 54 Dimensions Common for Master and Expansion Master Unit mm ...
Страница 78: ......
Страница 79: ...59 PART III I O Link Unit CQM1 LK501 ...
Страница 80: ......
Страница 88: ......
Страница 92: ......
Страница 93: ...73 PART IV Analog Input Unit and Analog Power Supply Units CQM1 AD041 CQM1 IPS01 CQM1 IPS02 ...
Страница 94: ......
Страница 118: ......
Страница 120: ......
Страница 121: ...101 PART V Analog Output Unit and Analog Power Supply Units CQM1 DA021 CQM1 IPS01 CQM1 IPS02 ...
Страница 122: ......
Страница 126: ......
Страница 140: ......
Страница 142: ......
Страница 144: ......
Страница 156: ......
Страница 172: ......
Страница 186: ......
Страница 187: ...167 PART VII Linear Sensor Interface Units CQM1 LSE01 CQM1 LSE02 ...
Страница 188: ......
Страница 192: ......
Страница 204: ......
Страница 218: ......
Страница 238: ......
Страница 242: ......
Страница 246: ......
Страница 248: ......
Страница 250: ......