Physical Layout of the Unit

Section 2-1

11

2-1-2

 LED Indicators

RUN  (green) : Unit status indication.

ON : Indicates  that  the  unit  is  receiving  power  from  the

CQM1  power  supply,  and  that  the  unit  has  initialised
properly.

Flashing : The unit is initialising.

ERR 

(red) : General error indication.

ON :  An  internal  hardware  problem  is  detected  during

power-on initialisation (RUN LED flashing).

Errors  in  the  data  transmission  between  slaves  and
the master.

A  requested  change  of  operation  mode  was  not  pos-
sible.

APF 

(red) : AS-Interface power fail indication.

ON :  The supply voltage on the AS-Interface line is too low

to guarantee reliable communication.

CER 

(red) : Configuration error.

ON :  The detected actual configuration is different from the

stored ’projected’ configuration.

AUP  (yellow) : Auto-programming is available.

ON :  One  slave  is  missing,  and  can  be  replaced  by  an

identical  slave  with  address  0,  when  the  master  is  in
Protected  Mode.  The  address  will  then  automatically
be set to that of the missing slave.

CM 

(yellow) : ON : The unit is in Configuration Mode or in Setup Mode.

1. Configuration Mode.

The AS-Interface master will automatically accept new
slaves  in  the  configuration,  and  start  I/O  data  ex-
change with them.

2. Setup Mode.

The  permanent  configuration  data  in  the  CQM1-ARM
can  be  modified,  slave  addresses  and  slave  parame-
ters can be read/written.

OFF : the unit is in Protected Mode.

Содержание CQM1-ARM21

Страница 1: ...CQM1 ARM21 AS Interface Master Unit OPERATION MANUAL Cat No W357 E1 1...

Страница 2: ......

Страница 3: ...CQM1 ARM21 AS Interface Master Unit Operation Manual Produced April 1999...

Страница 4: ...iv...

Страница 5: ...Wd in documentation in this sense The abbreviation PLC means Programmable Logic Controller and is not used as an abbreviation for anything else Visual Aids The following headings appear in the left c...

Страница 6: ...vi...

Страница 7: ...NS AND PERFORMANCE 17 3 1 Overall Specifications 18 3 2 Dimensions 19 3 3 Performance 19 4 PLC INTERFACE 25 4 1 PLC Settings 26 4 2 Internal Data Structures 27 4 3 Master Operation Modes 28 4 4 AS Int...

Страница 8: ...viii...

Страница 9: ...allation of the CQM1 ARM21 Section 3 describes the overall specifications and the communication performance of the Unit Section 4 describes the interface with the user Section 5 describes how to set u...

Страница 10: ...x...

Страница 11: ...tant for the safe and reliable application of the AS Interface Master Units You must read this section and understand the information contained before attempting to set up or operate an AS Interface M...

Страница 12: ...e to provide the systems machines and equipment with double safety mechanisms This manual provides information for installing and operating OMRON AS Interface Master Units Be sure to read this manual...

Страница 13: ...removing any Units e g I O Units CPU Unit etc or memory cassettes Assembling any devices or racks Connecting or disconnecting any cables or wiring Failure to abide by the following precautions could l...

Страница 14: ...en signal lines or momentary power interruptions Provide external interlock circuits limit circuits and other safety circuits in addition to any provided within the PLC to ensure safety 6 EC Directive...

Страница 15: ...ace This section provides a general introduction to AS Interface 1 1 Introduction 2 1 1 1 AS International 2 1 1 2 System Components 3 1 1 3 Technical Details 4 1 2 Master Functionality 7 1 3 Slave Fu...

Страница 16: ...available from 30 vendors OMRON is a full member of the AS International Association Positioning AS Interface is primarily aimed at the transfer of binary in and output data in industrial applications...

Страница 17: ...4 inputs 4 outputs 248 The slave s circuitry is generally powered via the AS Interface line but in and output ports may have a provision for external power supply Power Supply Superimposing communicat...

Страница 18: ...AND exchange I O data with slave stations over a simple unshielded two wire cable To achieve this while maintaining reliability and electromagnetic compatibility in an industrial environment a specif...

Страница 19: ...posed of the following elements Start bit Control bit 5 Bit Address 5 Bit Information Parity bit End bit ST 0 CB A4 A3 A2 A1 A0 I4 I3 I2 I1 I0 PB EB 1 Response After each master request the master wil...

Страница 20: ...he list of active slaves The master will cyclically try to re initialise the slave in the inclusion phase Performance The cycle time of an AS Interface network depends on the number of slaves that the...

Страница 21: ...sists of the M0 profile plus 2 additional functions to set and store slave parameters The CQM1 ARM21 provides M0 functionality in standard operation mode but additional configuration functions are ava...

Страница 22: ...sensor or other devices and elements Thus the profiles should help to increase the interchangeability of actuators and sensors A slave profile has a well defined and fixed I O configuration I O code w...

Страница 23: ...nstall an AS Interface system 2 1 Physical Layout of the Unit 10 2 1 1 Front Cover 10 2 1 2 LED Indicators 11 2 1 3 Switches 12 2 1 4 Connector 14 2 2 Mounting the CQM1 ARM21 14 2 3 AS Interface Netwo...

Страница 24: ...re the same as those of comparable CQM1 I O units For mounting instructions see the CQM1 Operation Manual The front of the unit features A removable front cover 23 LED indicators for unit status bus s...

Страница 25: ...ine is too low to guarantee reliable communication CER red Configuration error ON The detected actual configuration is different from the stored projected configuration AUP yellow Auto programming is...

Страница 26: ...on with more than 15 slaves this indicator will periodically turn OFF and ON to show the status of all slaves If set to 15 or fewer slaves this LED will remain OFF 2 1 3 Switches CH The switches 1 3 s...

Страница 27: ...BUS error in the CPU RSV Reserved Keep this switch in OFF position MOD Selects the operation mode of the AS Interface master OFF Configuration Mode Setup Mode In Configuration Mode the AS Interface ma...

Страница 28: ...Unit connect it to a CQM1 PLC just like other Units such as I O Units Refer to the PLC s Operation Manual for details on mounting Units to the PLC or installing the PLC in a control panel A label is s...

Страница 29: ...rated AS Interface slave function A hand held addressing device can be useful to build up the network but is not essential since the CQM1 ARM21 provides equivalent functionality when used in Setup Mod...

Страница 30: ...AS Interface Network Installation Section 2 3 16...

Страница 31: ...tion describes the overall specifications and the communication performance of the CQM1 ARM21 3 1 Overall Specifications 18 3 2 Dimensions 19 3 3 Performance 19 3 3 1 AS Interface Cycle Time 20 3 3 2...

Страница 32: ...words out Max No of Slaves per Master Unit Switch selectable With minimum IR words 11 slaves With maximum IR words 31 slaves Status information in PLC Operation Mode flag System Error flag Normal Ope...

Страница 33: ...etween the change of state of a data bit in the PLC memory and the moment that the corresponding output on a slave unit changes state Since AS Interface is an open bus system it is possible to use sla...

Страница 34: ...the next data exchange phase 0 168 ms after the start of the inclusion phase The 0 154 ms is the time taken by each master request slave response and the pauses in between The exact value of course de...

Страница 35: ...g seviced tMP1 Master processing time Start receiving slave response data available at the I O bus tRF I O refresh time Time required to update inputs and outputs of all CQM1 I O units tPE Program Exe...

Страница 36: ...s tRF I O refresh time Time required to update inputs and outputs of all CQM1 I O units tPE Program Execution time Processing of the PLC program and peripherals tPLC PLC Cycle time scan time tPE tRF t...

Страница 37: ...3 3 23 Optimisation The processing time in the PLC can be reduced by using the IORF instruction in the PLC program Interrupt input refresh Direct output refresh See the CQM1 CPM1 Programming manual W...

Страница 38: ...Performance Section 3 3 24...

Страница 39: ...ags 31 4 4 2 Control Bits 32 4 4 3 I O Data Bits 33 4 5 Setup Mode 34 4 5 1 Command Area 34 4 5 2 Response Area 36 4 5 3 Commands 37 4 5 3 1 No Command 37 4 5 3 2 Get_Permanent_Configuration 38 4 5 3...

Страница 40: ...4 EV1 NL CQM1 CPU45 EV1 NL Produced after 01 04 1999 at OMRON Manufacturing of the Netherlands Lot No 01 4 9 N With the above models support for the CQM1 ARM21 s I O range can be activated by setting...

Страница 41: ...data from the inputs of all active slaves Input data of inactive slaves is set to zero 0 LDS List of Detected Slaves In this list one bit is set for each slave 0 31 that is detected by the master thro...

Страница 42: ...s is set to default values FH PP Permanent Parameter This array contains the configured parameters of all slaves 1 31 created either by local configuration of the master using Set_Permanent_Parameter...

Страница 43: ...lave means a slave with its address set to 0 and the same type means with identical ID code and identical I O code This process is called Auto programming When the master detects one missing slave whi...

Страница 44: ...As a result all slaves will temporarily be reset Setup Mode Setup mode is not defined by the AS Interface Specification In Setup Mode the CQM1 ARM21 does not comply with the requirements of an AS Inte...

Страница 45: ...input word allocated to the Unit is indicated as IR n n 001 006 The first output word allocated to the Unit is indicated as IR m m 100 106 The Status Flags are inputs to the PLC Host system that indic...

Страница 46: ...anent configuration data 4 4 2 Control Bits IR m 00 Auto_Address_Disable Bit 0 Auto Addressing is enabled When the AS Interface master is in Protected Mode it is possible to replace slaves on line by...

Страница 47: ...lave 23 Slave 22 Slave 21 Slave 20 Inputs from slaves 20 23 IR n 6 Slave 27 Slave 26 Slave 25 Slave 24 Inputs from slaves 24 27 IR n 7 Slave 31 Slave 30 Slave 29 Slave 28 Inputs from slaves 31 28 D3 D...

Страница 48: ...figure an AS Interface system without the necessity of additional configuration tools Functions accessible to the user only in Setup Mode are Reading and writing of the permanent configuration data in...

Страница 49: ...and Code to 0 prepares the master for the next command Command Code 0 MUST be issued before each command 1 Get_Permanent_Configuration Returns the master s permanent configuration data for one slave a...

Страница 50: ...ord allocated in the CPU will contain the master s response to a command in addition to the status flags IR n 00 IR n 03 Status Flags See 4 4 1 Status Flags IR n 04 IR n 07 Command Status 0 No command...

Страница 51: ...make sure that the Mode Flag is ON before a command is sent If the Mode Flag is OFF e g due to the MOD switch forcing the unit to stay in Protected Mode switch ON the master will interpret the comman...

Страница 52: ...error other Master is busy Permanent Configuration Data for slave Command Argument 1 1 byte hexadecimal code representing I O Code and ID Code 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 IR n I O ID 0 0 0 1...

Страница 53: ...1 0 Command Argument 2 IR m 1 I O ID ID Code I O Code See Appendix B AS Interface Slave Profiles for a list of ID codes and I O codes Command Status 1 Command processed 2 Error in processing the comma...

Страница 54: ...Master is busy Actual Configuration Data for slave Command Argument 1 1 byte hexadecimal code representing I O Code and ID Code 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 IR n 0 0 0 1 1 Setup Mode Command...

Страница 55: ...nd Status 1 the command was processed successfully If not the following flags indicate the type of error 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 IR n 0 0 1 0 1 Setup Mode Command Status Error Slave not...

Страница 56: ...No_Command 0 2 X previous data 0 0 0 D Master Ready Send Command 3 1 2 3 7 2 0 0 1 D OK Example 2 Change the address of slave 1 to 31 while slave 31 already exists on the network Command IR101 IR100 R...

Страница 57: ...command invalid argument value or EEPROM read error other Master is busy Permanent Parameter Data of slave Command Argument 1 4 bits as below 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 IR n P3 P2 P1 P0 0 0...

Страница 58: ...1 0 IR m 1 P3 P2 P1 P0 Parameter Data Command Argument 2 The meaning of Parameters P0 P4 is slave specific Command Status 1 Command processed successfully 2 Error in processing the command invalid arg...

Страница 59: ...rgument value or Slave read error other Master is busy Permanent Parameter Data of slave Command Argument 1 4 bits as below 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 IR n P3 P2 P1 P0 0 0 0 1 1 Setup Mode...

Страница 60: ...nt value or Slave write error other Master is busy Result of the Write_Parameter Command error flag If all error flags are off and Command Status 1 the command was processed successfully If not the fo...

Страница 61: ...ile the switches can be operated locally If the MOD switch is set from OFF to ON while in Setup Mode the ERR LED will light to indicate that the requested mode change could not be made The user is to...

Страница 62: ...Setup Mode Section 4 5 48...

Страница 63: ...complete AS Interface network 5 1 AS Interface Set up Methods 50 5 2 Bottom up Method 50 5 2 1 Bottom up with addressing unit 50 5 2 2 Bottom up without addressing unit 51 5 3 Top down Method 51 5 3 1...

Страница 64: ...k will be stored as projected configuration and once in Protected Mode the master will communicate with all these slaves even if slaves of the wrong type or the wrong address have been installed In th...

Страница 65: ...e safest way to set up the AS Interface network The projected slave configuration can be defined in advance and stored in the master unit When installing the system the user can easily verify if the a...

Страница 66: ...o address 0 they need to be added and re programmed one by one 1 2 3 1 Connect the AS Interface cable and power supply to the CQM1 ARM21 2 Put the master in Setup Mode MOD switch OFF Mode bit IR m 01...

Страница 67: ...ce operations needed to keep the AS Interface Master Unit operating properly 6 1 Error indicators 54 6 2 Troubleshooting 54 6 2 1 PLC Errors 54 6 2 2 Start up Problems 55 6 2 3 Configuration Problems...

Страница 68: ...o indicate that its initialisation could not be completed Symptoms Possible cause Possible remedy An I O unit or the end cover is not connected properly Turn the PLC s power OFF and check for loose un...

Страница 69: ...pplies from standard types 6 2 3 Configuration Problems When encountering problems during the configuration of an AS Interface network check the table below Symptom Possible cause Possible remedy CER...

Страница 70: ...alfunctions or bad connections Error response to a Setup Mode command affecting actual slaves Slave address is above the limit set by the CH switches Use only slave addresses within the range selected...

Страница 71: ...ta exchange with the slave via the allocated IR bits If necessary replace the slave Slave status LED is flashing Slave 0 LED flashing indicates that a slave with address 0 is detected Assign a valid a...

Страница 72: ...dition In general inspect the system once every 6 to 12 months but inspect more frequently if the system is used with high temperature or humidity or under dirty dusty conditions Inspection Equipment...

Страница 73: ...ction contains additional information concerning AS Interface specifications and terminology Appendix A AS Interface PICS 60 Appendix B AS Interface Slave Profiles 63 Appendix C AS Interface terminolo...

Страница 74: ...ist31 13 Status List31 Get_LPS 14 Status List31 Get_LAS 15 Status List32 Get_LDS 16 0 Status Flags Get_Flags 16 1 Status Flag Get_Flag_Config_OK X CER LED Status Flag n 03 2 1 2 4 4 1 16 2 Status Flag...

Страница 75: ...ED Status Flag n 03 2 1 2 4 4 1 16 2 Status Flag Get_Flag_LDS 0 16 3 Status Flag Get_Flag_Auto_Address_Assign 16 4 Status Flag Get_Flag_Auto_Prog_Available X AUP LED 2 1 2 16 5 Status Flag Get_Flag_Co...

Страница 76: ...62...

Страница 77: ...virgin R reserved Defined slave profiles exist for I O X ID F Free profiles I O X ID 0 Remote I O ports I O 0 ID 1 Two dual signal sensors I O 3 ID 1 One dual signal sensor one dual actuator I O 8 ID...

Страница 78: ...face line and capable to communicate properly address assignment Replacement of the existing address of the AS Interface slave with a new address address An address out of the address space of the AS...

Страница 79: ...the master The list is available in the master list of detected slaves A list of all slaves actually detected by the master The list is available in the master list of projected slaves A list of all c...

Страница 80: ...66...

Страница 81: ...ication Problems 57 Specification See Specification AS Interface Configuration Functions 18 35 Mode See Mode Network 50 52 Problems 55 Store 13 50 52 Connector 14 18 Control Bits 32 Auto_address_disab...

Страница 82: ...e Mode R Response area 36 Response time 19 21 Retransmission 20 RSV See Switches RUN See Indicators S SET See Switches Setup Mode See Mode Slave Address 3 Indicators 12 IO ID codes Profiles 3 8 29 63...

Страница 83: ...catalog number on the front cover of the manual Cat No W357 E1 1 Revision code The following table outlines the changes made to the manual during each revision Page numbers refer to the previous versi...

Страница 84: ......

Страница 85: ...Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 NL 2132 JD Hoofddorp The Netherlands Tel 31 0 23 568 1300 Fax 31 0 23 568 1388...

Страница 86: ...Authorized Distributor Cat No W357 E1 1 Note Specifications subject to change without notice Printed in the Netherlands...

Отзывы: