Physical Layout of the Unit
Section 2-1
12
0~15 (yellow) : Slave status indicators.
ON :
A slave is active, i.e. exchanging I/O data with the
master.
Flash : A slave is in the list of projected slaves, but not ac-
tive.
Slave 0 cannot be an active slave; if LED 0 flashes, a slave
with address 0 has been detected on the network.
+16 (yellow) : OFF : the status of slaves 0-15 is shown;
ON
: the status of slaves 16-31 is shown.
If the setting of the CH switches 1-3 allows communication
with more than 15 slaves, this indicator will periodically turn
OFF and ON, to show the status of all slaves. If set to 15 or
fewer slaves, this LED will remain OFF.
2-1-3
Switches
CH
The switches 1-3 select the number of IR words that the CQM1-
ARM21 will occupy in the CPU. This setting will influence the maxi-
mum number of AS-Interface slaves that can be addressed by the
PLC, and therefore the maximum number of I/O points that can be
connected.
SW3
SW2
SW1
IR words
in + out
Highest AS-I
slave address
Max. AS-I
I/O points
OFF
OFF
OFF
3 + 3
11
44 / 44
OFF
OFF
ON
4 + 4
15
60 / 60
OFF
ON
-
6 + 6
23
92 / 92
ON
OFF
OFF
5 + 5
19
76 / 76
ON
OFF
ON
6 + 6
23
92 / 92
ON
ON
-
8 + 8
31
124 / 124
Содержание CQM1-ARM21
Страница 1: ...CQM1 ARM21 AS Interface Master Unit OPERATION MANUAL Cat No W357 E1 1...
Страница 2: ......
Страница 3: ...CQM1 ARM21 AS Interface Master Unit Operation Manual Produced April 1999...
Страница 4: ...iv...
Страница 6: ...vi...
Страница 8: ...viii...
Страница 10: ...x...
Страница 30: ...AS Interface Network Installation Section 2 3 16...
Страница 38: ...Performance Section 3 3 24...
Страница 62: ...Setup Mode Section 4 5 48...
Страница 76: ...62...
Страница 80: ...66...
Страница 84: ......