9-4 Input voltage sensitivity settings
BL50T/BL75T/BL100T
82
9-4 Input voltage sensitivity settings
The relationship between the input voltage sensitivity settings and the input/output
voltages of the Uninterruptible Power Supply (UPS) is as shown in the following table.
Select the input voltage sensitivity setting that suits the range of the input voltage
specifications of the connected devices.
Input voltage
sensitivity
UPS input voltage range
UPS output voltage range
How to select an input
voltage sensitivity setting
High sensitivity
setting
94 to 106VAC
More than 106VAC or less than
94VAC
94 to 106VAC
100VAC±
3%
If you want to narrow the
output voltage range as
much as possible
Standard
setting
92 to 108VAC
More than 108VAC or less than
92VAC
92 to 108VAC
100VAC±
3%
When using in an ordinary
environment
Low sensitivity
setting
89 to 110VAC
More than 110VAC or less than
89VAC
AC89V to 110V
AC100V±
3%
If you want to operate the
UPS by keeping the
frequency of fan operation
low
Содержание BL100T
Страница 17: ...1 Preparation 1 2 Check the accessories BL50T BL75T BL100T 17...
Страница 21: ...1 Preparation 1 5 I O circuit block diagram BL50T BL75T BL100T 21 1 5 I O circuit block diagram...
Страница 23: ...2 Installation and connection 2 1 Install BL50T BL75T BL100T 23 2 Do not install in any of the following ways...
Страница 73: ...7 How to use optional cards 7 3 SNMP Web card BL50T BL75T BL100T 73 7 7 3 SNMP Web card LAN 10 100...
Страница 80: ...9 References 9 2 Dimensions BL50T BL75T BL100T 80 9 2 Dimensions Unit mm Tolerance 2mm BL50T BL75T BL100T...