3 Check and start the operation
3-4Operation by using the LCD menu
BL50T/BL75T/BL100T
45
3
☆
: Displayed only when the UPS is stopped. Not displayed while the UPS is running.
Menu item
Description
Value
Menu Type
Settings
Battery Settings
Low Battery Warning
☆
Set the level at which a low battery warning
can be detected.
Low battery warning:
Initial setting (factory default), Level
change: 0 to 100%
Advanced
Dry Contact
BMS setting (Note 3)
Temporarily stop communication between
the CPU in the battery pack (BMS) and the
CPU in the CPU when replacing the
battery.
BMS mode enabled/disabled
(Factory default) Enabled
BSsignal
ValidRange
☆
Set the condition for BS signal reception.
BS signal valid range:
Always enabled (factory default),
Only for backup operation
BSsignal
Delay Time
Set the delay time for a BS signal.
BS signal delay time:
0 to 9000 seconds, or 9999 seconds
(Factory default: 0 second)
BUsignal
Delay Time
Set the delay time for a BU signal.
BU signal delay time:
0 to 180 seconds
(Factory default: 0 second)
Dry Contact Logic
Set the dry contact logic.
Dry Contact logic:
BU, BL, TR, WB:
Normal (factory default)/
Reverse
Remote ON/OFF
Logic
☆
Set the remote signal logic.
This setting is common to a contact signal
I/O card and remote ON/OFF dedicated
connector.
Remote ON/OFF logic:
OFF when short-circuited (factory default),
OFF when opened, Disabled
Identification
Type
Display the names of the UPS and battery
pack.
Type name:
UPS: Model.
Battery: Model
Standard
Serial Number
Display the serial number of the UPS.
Serial number:
S/N: xxxxxxxxxxxxxxxG
Firmware Version
Display the firmware version of the UPS.
Firmware version:
UPS: M:x.xx
USB: S:x.xx
Advanced
Memorandum
Information up to 20 alphanumeric
characters can be viewed.
-
Log
Fault Log
Display up to 10 logs of faults that occurred
in the past (time of occurrence and fault
details).
Fault log:
Year/month/day/hour/minute, message
Standard
Shutdown Log
Display up to 10 reasons for UPS
shutdown.
Shutdown log:
Year/month/day/hour/minute, message
AC input Log
Display up to 10 logs of events that
occurred in the past.
AC input log:
Year/month/day/hour/minute, message
Reset All Log Data
Clear each piece of log data.
Execute Reset All Log Data
Note 1: Refer to "9-4 Input voltage sensitivity settings".
Note 2: Refer to "9-3 Battery life".
Note 3: BMS stands for Battery Management System.
A lead battery UPS does not require the BMS.
A lithium battery UPS always are safely managed a battery condition using the
BMS.
Содержание BL100T
Страница 17: ...1 Preparation 1 2 Check the accessories BL50T BL75T BL100T 17...
Страница 21: ...1 Preparation 1 5 I O circuit block diagram BL50T BL75T BL100T 21 1 5 I O circuit block diagram...
Страница 23: ...2 Installation and connection 2 1 Install BL50T BL75T BL100T 23 2 Do not install in any of the following ways...
Страница 73: ...7 How to use optional cards 7 3 SNMP Web card BL50T BL75T BL100T 73 7 7 3 SNMP Web card LAN 10 100...
Страница 80: ...9 References 9 2 Dimensions BL50T BL75T BL100T 80 9 2 Dimensions Unit mm Tolerance 2mm BL50T BL75T BL100T...