3 Check and start the operation
3-4Operation by using the LCD menu
BL50T/BL75T/BL100T
43
3
3-4-2 LCD menu item list
・
Japanese (factory default) or English can be selected for the display language.
・
The displayed items differ depending on the menu type set. The standard type and the
advanced type are available. The standard type (factory default) is intended for
general users. The advanced type is intended for the administrator.
References
・
To set English for the display language, select [Settings] - [Local Setting] -
[Language].
・
To display the advanced type menu, select [Settings] - [Local Setting] - [Menu Type].
☆
: Displayed only when the UPS is stopped. Not displayed while the UPS is running.
Menu item
Description
Value
Menu type
Measurements
Load Meter
Display the load amount in VA and W.
Load amount:
0 to xxxx W
0 to xxxx VA
Standard
Input/Output Meter
Display the input and output
voltages/frequencies of the UPS.
Input/output:
Input: 0 to xxx.x V, 0 to xx.x Hz
Output: 0 to xxx.x V, 0 to xx.x Hz
Battery Meter
Display the status of the built-in battery.
Battery:
Charged level: 0 to 100%
Voltage: 0.0 to xxx.xV
Operating time (backup time):
0.0 to xxx min
Longevity
Display the expected life of the UPS in five
levels.
Life:
UPS: Displays as level
□
in five levels.
Battery: Displays as level
□
in five levels.
Cumulat. Power Usage
Display the amount of electric power used
so far and the number of elapsed days.
Cumulative power usage:
Total: 0 to xxxx kWh
Number of days: 0 to xxxx days
Advanced
Average Power Usage
Display the average of the amounts of
electric power used so far.
Average power usage:
0 to xxxx Wh
Control
Start Function Test
Conduct a simple self-diagnostic test on
battery deterioration and show its result.
Start self-diagnostic test
- Battery test: Pass
- Battery test: Fail
(Battery not connected, battery
deteriorated)
- Battery test: Cancel
(Operating in battery mode, not charged
adequately)
Standard
Reset B.life counter
Reset the battery life counter.
Execute battery life counter reset
Reset Power Usage
Reset the values for the cumulative power
usage and average power usage.
Execute cumulative power usage reset
Advanced
Dry Contact Test
☆
Conduct a contact test when using a
contact signal I/O card (SC07/SC08).
Execute a contact signal test
BU: ON/OFF
BL: ON/OFF
TR: ON/OFF
WB: ON/OFF
Initialization
☆
Restore the factory default settings of the
UPS.
Execute settings initialization
Maintenance Bypass
☆
Forcibly shift to the bypass mode.
Execute maintenance bypass
Settings
Local Setting
Language
Set the language displayed on LCD.
Display language: Japanese (factory
default), English
LCD Setting
Change the contrast for LCD.
Set the LCD (contrast bar)
LCD Auto OFF
Set the time until the LCD automatically
turns off.
LCD Auto OFF: Always ON (factory
default), Auto OFF 30 seconds, Auto OFF 3
minutes
LCD Test
Check that the LCD and LEDs turn on.
Execute LCD test
Содержание BL100T
Страница 17: ...1 Preparation 1 2 Check the accessories BL50T BL75T BL100T 17...
Страница 21: ...1 Preparation 1 5 I O circuit block diagram BL50T BL75T BL100T 21 1 5 I O circuit block diagram...
Страница 23: ...2 Installation and connection 2 1 Install BL50T BL75T BL100T 23 2 Do not install in any of the following ways...
Страница 73: ...7 How to use optional cards 7 3 SNMP Web card BL50T BL75T BL100T 73 7 7 3 SNMP Web card LAN 10 100...
Страница 80: ...9 References 9 2 Dimensions BL50T BL75T BL100T 80 9 2 Dimensions Unit mm Tolerance 2mm BL50T BL75T BL100T...