Safety Accessories Supplementary Sheet
20
OMICRON
4.5
Disconnection
To disconnect the
SAA1
from the main device:
1. Make sure that the main device to which the
SAA1
is connected to is switched off.
WARNING
Death or severe injury caused by high voltage or current possible.
Observe the five safety rules (see 1.2.2 Five safety rules).
2. Press the
Emergency Stop
button on the main device or test system (in case of
VOTANO 100
the
Emergency button
on
SAB1
safety box) and lock the main device with a physical key (
CPC 80
and
CPC 100
)
or by pressing the software lock button (
TESTRANO 600
).
NOTE!
CIBANO 500
and
COMPANO 100
do not have a separate physical key nor a software lock
function.
3. Disconnect the test system from the asset under test as described in the User Manual of the main
device.
4. Loosen the locking screws on the
Safety Connector Dongle
attached to the
SAA1
Beeper Dongle
and disconnect the
Safety Connector Dongle
from
SAA1
. In case of
VOTANO 100
disconnect the
SAB1
safety box connector from
SAA1
.
5. Loosen the locking wheels on the
SAA1
and disconnect the
SAA1
Beeper Dongle from the main
device
SAFETY
output connector.
6. Insert the
Safety Connector Dongle
into the main device
SAFETY
output connector and tighten the
locking screws. In case of
VOTANO 100
insert the
SAB1
connector into the
SAFETY
output
connector of VBO2.
7. The
SAA1
has now been removed and the main device has the required
Safety Accessory Dongle
installed on the
SAFETY
output connector.
4.6
Cleaning
To clean the
SAA1
, use a cloth dampened with isopropanol alcohol.
WARNING
Death or severe injury caused by high voltage or current possible.
Before cleaning the
SAA1
, always disconnect it from the test system.