C.2 Analog 0-10 V Sensor Interface P/N ANA-010V
0-10V DC or 0-5V DC signals are common outputs for many industrial transmitters, that measures
variables such as: temperature, flow, pressure, distance, humidity, voltage, current and more. The
Datalog X-PRO 0 to- 10V interface converts this analog signal to digital and sends it to the Internet
for subsequent analysis.
C.2.1 D.C. Electrical Characteristics
PARAMETER
Ratings
Supply Voltage from Datalog X-PRO
3.3 V DC
Input Voltage Range
0 – 11 V DC
Maximum Input voltage of a Channel
11 V DC using a 450 Ohm Series Resistor
C.2.2 Specification
PARAMETER
Operational Range
Temperature
41°F – 104°F (5°C to 40 °C)
Relative humidity
25-75 %
Accuracy
0.25 V at reference conditions
Resolution
0.01V
Digital Conversion Range
0 to 1100
Output: 0 = 0 VDC / Output: 1100 = 11 VDC
C.2.3 Connection Diagram
Figure C2-1 0 -10 Volts Interface connection with External Terminal Box.
DO NOT REMOVE THE 450
Ω
/1 WATT RESISTORS in analog 0-10V input channel.
www.omicroning.co March 2020
50