Section 4: Electrical Installation Foreword
Consider implementing safeguards independent to
Datalog X-PRO when designing the wiring and
grounding plans for your application. This helps to assure optimum system operation, provides
additional electrical noise protection for your application and the
Datalog X-PRO
, and prevents
any malfunction on the process due to unexpected operating failures, to which any electronic
system is susceptible.
4.1 Power Requirements
Among other hardware and firmware protections,
Datalog X-PRO is protected against power
interruptions through its battery; which can provide power for up to 180 days, depending on the
sensors implemented and the period between messages sent to a remote platform, aiming to
keep safe monitoring and storage of data. The user may consider using the Datalog X-PRO
disconnected from a power source and recharging the device when the battery is almost empty.
Always observe the following safety instructions:
●
Connections must be made only in the complete absence of line voltage.
●
If over-voltage is expected, surge arresters should be used.
●
The power adapter provided with the equipment (P/N GSM06U12-P1J) is
only for indoor use.
Use only a safety-certified power adapters or an
Industrial Power Supply with dual insulation
between the primary and
output for powering the unit. The power supply output rating must be
limited to 6-24V DC, 0.5A for a single
Datalog X-PRO
, and not to be
connected to a AC or DC distribution network.
●
For outdoor use, the user could use a safety-certified and waterproof
approved Solar Panel (not provided); the output rating must be limited to
6-24V DC, 0.
5A for a
single
Datalog X-PRO.
In any case, a 0.5A 6W fuse and circuit breakers should be used between
the power supply and the device.