Resistance
7 - 11
Test settings
Figure 7:
RWinding
test card
with test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Range:
output range
Note:
The
400A DC
output range provides maximum current 100 A.
Itest:
nominal test current
R min:
calculated minimum winding resistance value (display only).
Depends on the value of the nominal test current and the
measuring range:
– 400A DC: Rmin = 0.2mV / Itest
– 6A DC: Rmin = 0.2mV / Itest
– V DC (2 wire): Rmin = 0.2
Ω
R max:
calculated maximum winding resistance value (display only).
Depends on the value of the nominal test current and the
measuring range:
– 400A DC: Rmax = 5V / Itest.
– 6A DC: Rmax = 10V / Itest.
– V DC (2 wire): Rmax = 20k
Ω