CPC 100 V1.41
8 - 22
Press the A
D D
R
A M P
button, and repeat steps
to
to define additional
ramps. Note that the maximum possible number of ramps is 5.
Ramping differentiates two "Overload" trigger conditions:
– the occurrence of an overload (as described above)
– the clearing of an overload condition.
Note:
Clearing of an overload condition means: the CB closes
again. For debouncing purposes, at CB closing time
measurements,
CPC 100
adds a fixed time of 100ms to the
measured value. In order to determine the true CB closing time
value, these 100ms need to be deducted from the value displayed
in the measurement table (refer to the following example).
– The feature M
A N U A L
T
R I G G E R
provides a possibility to manually
initiate a trigger signal (that is, a premature termination) of the
current ramp at any time. This manual trigger has the same
function as an automatic trigger signal.
Trigger threshold.
Only available if a trigger ">" or "<" was selected (refer to
).
9
cont.
10
9
7
10
Содержание CPC 100
Страница 12: ...CPC 100 V1 41 x...
Страница 28: ...CPC 100 V1 41 1 16...
Страница 90: ...CPC 100 V1 41 3 14...
Страница 194: ...CPC 100 V1 41 6 30...
Страница 250: ...CPC 100 V1 41 8 32 Figure 24 Settings of Amplifier test card for this example use case...
Страница 258: ...CPC 100 V1 41 9 4...
Страница 264: ...CPC 100 V1 41 10 6...
Страница 282: ...CPC 100 V1 41 12 10 Figure 9 Saving tests with the CPC Editor...
Страница 284: ...CPC 100 V1 41 12 12...
Страница 312: ...CPC 100 V1 41 14 12...
Страница 316: ...CPC 100 V1 41 15 4...
Страница 350: ...CPC 100 V1 41 16 34...
Страница 370: ...CPC 100 V1 41 17 20 7 Finish the assembly by screwing the backnut to the housing and by tightening them with wrenches...
Страница 372: ...OMICRON Contact Addresses 22...