![Omicron CPC 100 Скачать руководство пользователя страница 245](http://html2.mh-extra.com/html/omicron/cpc-100/cpc-100_reference-manual_3988877245.webp)
Others - Ramping
8 - 27
Testing PickUp/DropOff Value of an Overcurrent
Relay
To determine the pick up and the drop off value of a relay, a series of three
ramps is defined. The first ramp determines the pick up value, the second one
represents a 1s pause time, and the third ramp determines the drop off value.
Figure 19:
Setup for testing the
pick up and drop off
values of an
Overcurrent relay
The
CPC 100
AC OUTPUT
feeds the ramped current signal into a CT, which is
connected to an overcurrent relay. The overcurrent relay’s trip contact is fed into
CPC 100
binary input
BinIn
, and acts there as a trigger signal (as described on
I>