Figure 6-14. Logging Settings Screen
To start an internal logging session:
1. Select “Transmitter Internal Logging” to On.
2. Set the “Internal Logging Sampling Rate” from the dropdown menu
3. Select “Circular Buffer” to ON/OFF.
• If the circular buffer is ON, after the transmitter internal memory is full, new
measurements will be overwritten over previously saved measurements
starting with the oldest saved data point. This will continue until you turn the
logging off.
• If the circular buffer is OFF, the transmitter will stop logging when its memory
becomes full. Full memory is indicate by the yellow and red LEDs on the
transmitter blinking alternatively.
4. Click on “Save All Settings”. When the transmitter starts logging internally, the green
LED on the transmitter will blink twice every 3-seconds.
Restore Defaults:
The “Restore Defaults” button allows you to restore the factory default settings
on the UWBT transmitter. The settings that will be restored are: sensor sub-type,
engineering units, alarms and offset, and logging settings. For example, the
default settings for thermocouple transmitters are:
• Sub type: K calibration
• Engineering units: °F
• Temperature high alarm: 2300°F
• Temperature low alarm: -148°F
• Temperature deadband: 1°F
Software Instructions (PC App)
6
6-15