y
Range:
OME-ET-7000/OME-PET-7000 modules provide a programmable input
voltage/current range on all analog inputs channels, where a different range can
be set for each individual analog input channel. Select the required
voltage/current from the respective drop-down menus. For more detailed
technical specifications related to the input range for each analog input channel,
please refer to:
“Appendix
D
. Analog Input Type and Data Format Table”.
y
Enable
: This section allows each analog input channel to be switched ON or
OFF.
y
Normal/Fast Mode:
OME-ET-7000/OME-PET-7000 modules support sample
rates in
either “Normal” or “Fast” mode. Fast mode uses
60 Hz with a 12-bit
resolution, while Normal mode uses 10 Hz with a 16-bit resolution.
y
50/60Hz Rejection for AI:
In order to remove the noise from the power supply,
OME-ET-7000/OME-PET-7000 analog input modules feature two built-in
rejection filters, that operate at different frequencies, 50 or 60 Hz, that are
designed to remove noise generated by different power supplies.
y
AI Data Format:
OME-ET-7000/OME-PET-7000 modules allow data to be
displayed in either hexadecimal or engineering unit format. For more detailed
technical specifications related to the data format for each analog input channel,
please refer to:
“
Appendix D
. Analog Input Type and Data Format Table”.
Содержание OME-ET-7000 Series
Страница 1: ......
Страница 2: ......
Страница 16: ...Page 11 For the OME ET 7000 OME PET 7000 72 x 123 x 35 I have a strong mind I can finish anything...
Страница 37: ...Page 32 The lower section of the page provides a brief introduction to the web interface...
Страница 86: ...Page 81 After completing the configuration click the Submit button to save the settings 1 2...
Страница 92: ...Page 87 The default URL that the More Information item will link to http www omega com...
Страница 158: ......
Страница 159: ......