Page: 80
Step 3
Κ
Κ
Configure the Modbus Settings for the OME-PET-7026
Click the “
Pair
Connection
” option in the “
Configuration
” section of
the Main Menu and enter the details noted in the table below info the
respective fields.
Field
Settings
I/O Pair
Connection
Select this option to enable the I/O pair connection
functions.
Remote IP
Address
This is the IP address of the OME-ET-7017 (e.g.
192.168.1.204)
Remote TCP Port
502
Connection
Timeout
3000 ms
Reconnect Interval 5000 ms
Remote Net ID
1 (Default = 1, the Net ID for the OME-ET-7017)
To
determine the Net ID, check the “Modbus Definition” section on the
“Common Function” page, which can
be found by clicking the “Module I/O
Settings” option in the “Configuration” section of the Main Menu.
Scan Time
300 ms
Access Type
Select AO
Local AO Base Address
0, (Starting from AO0 on the OME-PET-7026)
Remote AI Base
Address:
0, (Starting from AI0 on the OME-ET-7017)
I/O Count
2, (Using AO0, AO1 and AI0, AI1)
Communication Timeout
400 ms