Page: 115
5.3. RTD Calibration
Type Code
The following table shows all of the type code for use in RTD calibration.
Type Code
20 ~ 29 2E
2F
80 81
83
2B
2C
82
2A
2D
Zero Calibration
Resistor
0
Ω
0
Ω
0
Ω
Span Calibration
Resistor
375
Ω
200
Ω
3200
Ω
Modbus Address for Calibration
Register
Points
Description
Access Type
00830
1
Enable/Disable Calibration
0=Disabled
1=Enabled
R/W
00831
1
Zero calibration command of ch0, 1=run
W (Pulse)
00832
1
Span calibration command of ch0, 1=run
W (Pulse)
00833
1
Zero calibration command of ch1, 1=run
W (Pulse)
00834
1
Span calibration command of ch1, 1=run
W (Pulse)
00835
1
Zero calibration command of ch2, 1=run
W (Pulse)
00836
1
Span calibration command of ch3, 1=run
W (Pulse)
00837
1
Zero calibration command of ch3, 1=run
W (Pulse)
00838
1
Span calibration command of ch3, 1=run
W (Pulse)
00839
1
Zero calibration command of ch4, 1=run
W (Pulse)
00840
1
Span calibration command of ch4, 1=run
W (Pulse)
00841
1
Zero calibration command of ch5, 1=run
W (Pulse)
00842
1
Span calibration command of ch5, 1=run
W (Pulse)
The calibration procedure is similar to the section 5.1. However, the RTD calibration
required an external resistor and must be calibrate for each channel rather than just
the ch0 we mentioned before.
Содержание OME-ET-7000 Series
Страница 1: ......
Страница 2: ......
Страница 16: ...Page 11 For the OME ET 7000 OME PET 7000 72 x 123 x 35 I have a strong mind I can finish anything...
Страница 37: ...Page 32 The lower section of the page provides a brief introduction to the web interface...
Страница 86: ...Page 81 After completing the configuration click the Submit button to save the settings 1 2...
Страница 92: ...Page 87 The default URL that the More Information item will link to http www omega com...
Страница 158: ......
Страница 159: ......