Page: 79
Step 1
Κ
Κ
Log in to the OME-PET-7026 web interface
Enter the IP address of the OME-PET-7026 in the browser, and then
enter your user name and password to log in to the OME-PET-7026
web interface. Refer to chapter 3,
“
Web Applications
”,
for more
details.
Step 2
Κ
Configure the AO type for the OME-PET-7026
Click the “
Module I/O Settings
” option in the
configuration section of
the Main Menu to open
the “
analog Output Settings
” page
and set
the voltage/current range to
“
-5 V - 5V
”
, and then click the
“
Submit
”
button. (Follow the same procedure to set the AI range for the
OME-ET-7017)
Tips & Warnings
The settings for both the AO type for the OME-PET-7026 and the AI
type for the OME-ET-7017 must be the same. In this example, they
are both “
-5 V ~ 5 V
”.
1