4.5.8. 16 (0x10) Write Multiple Registers
This function code is used to write a block of contiguous registers in an
OME-ET-7000/OME-PET-7000 module. The requested written values are specified
in the request data field. Data is packed as two bytes per register.
The normal response returns the function code, starting address, and quantity of
registers written.
Here is an example of a request to write two AO registers starting at AO0:
Request
Response
Field Name
(Hex)
Field Name
(Hex)
MBAP Header
01
MBAP Header
01
02
02
00
00
00
00
00
00
06
06
Unit Identifier
01
Unit Identifier
01
Function Code
10
Function Code
10
Starting Address Hi
00
Starting Address Hi
00
Starting Address Lo
00
Starting Address Lo
00
Quantity of Registers
Hi
00
Quantity Value Hi
00
Quantity of Registers
Lo
02
Quantity Value Lo
02
Byte Count
04
Registers Value Hi
00
Registers Value Lo
0A
Registers Value Hi
01
Registers Value Lo
02