Page: 53
y
Range:
In a manner, a different range can be set for each individual analog
output channel. Select the required voltage/current range from the respective
drop-down menus. For more detailed technical specifications related to the
output range for each analog output channel, please refer to: "Appendix E.
Analog Output Type and Data Format Table".
y
Slew Rate:
This is the programmable output slew rate for the analog output
channels, i.e., the rate of change in the analog output voltage/current as it
changes from one output voltage/current to another. Select the most appropriate
value from the respective drop-down menus.
y
Power-on Value
: A power-on value can be set for a specific analog output
channel, and the analog output channel will then generate the start-up value
output.
y
Safe Value:
When communication between the Host PC and the
OME-ET-7000/OME-PET-7000 module is interrupted, the analog output
channels can generate a predefined safe value. This function can be enabled or
disabled by configuring the Host WDT Timeout setting.
For a more detailed description of these Modbus functions, please refer to:
“Appendix
C. Modbus Application Notes
”.
Содержание OME-ET-7000 Series
Страница 1: ......
Страница 2: ......
Страница 16: ...Page 11 For the OME ET 7000 OME PET 7000 72 x 123 x 35 I have a strong mind I can finish anything...
Страница 37: ...Page 32 The lower section of the page provides a brief introduction to the web interface...
Страница 86: ...Page 81 After completing the configuration click the Submit button to save the settings 1 2...
Страница 92: ...Page 87 The default URL that the More Information item will link to http www omega com...
Страница 158: ......
Страница 159: ......