5.3.9.2
PANEL NETWORK PARAMETERS
The name of the panel and its ID can be configured here and are used for easier identification of the panel in
the
panel network
, from the other connected panels.
Another setting that can be configured, is the detection of faulty connections in case of a closed ring panel
network topology. The option is applied to all panels in the network by pressing the “APPLY TO NETWORK”
button (pressing the “SAVE” button, only panel name and ID are saved).
Figure 51
5.3.9.3
GROUP FORMATION
The formation of a network of panels, with all the connected panels, can be started
here using the “
START
”
button.
When the “AUTO ID” option is enabled (automatic ID), the IDs of the panels are automatically adjusted
starting from 1 and incrementing by one for each panel in the group.
If the “AUTO ID” option is disabled
(manual ID), the IDs of the panels won’t be changed during the procedure. If two or more panels have the
same ID, the group formation will fail, and the ID conflict must be manually handled. It is recommended to use
the automatic ID assignment.
Figure 52