ETR-9040-
Power Input
4 90-264VAC, 50/60Hz
5 11-26VAC or VDC
Example:
Standard Model:
ETR-9040-4110
• 90-264VAC operating
voltage
• Input: Standard Input
• Output 1: Relay
• Option: None
Signal Input
1 Standard Input
Thermocouple J, K,
T, E, B, R, S, N, L
RTD: PT100 DIN,
PT100 JIS
mV: 0~60MV
2 Voltage: 0-1V
3 Voltage: 0-10V
4 Current: 0-20mA
Option
0 None
1 Form A Relay
2A/240VAC
2 Pulsed voltage to
drive SSR, 5V/30mA
6 Triac Output,
1A/240VAC, SSR
7 Isolated 20V/25mA DC
Output Power Supply
8 Isolated 12V/40mA DC
Output Power Supply
9 Isolated 5V/80mA DC
Output Power Supply
A RS-485
B Event Input
Output 1
1 Form C Relay Rated
2A/240VAC
2 Pulsed Voltage to
Drive SSR,
5V/30mA
6 Triac Output
1A/240VAC, SSR
□ □ □ □
2
3
4
1
Section 2: CATALOG NUMBERING SYSTEM
Section 3: SPECIFICATIONS
2
Sensor
Input Type
Max. Range F°
Accuracy F°
Max. Range C°
Accuracy C°
J
Iron/Constantan
–58 to 1832°F
±3.6°F
–50 to 1000°C
±2°C
K
Chromel/Alumel
–58 to 2500°F
±3.6°F
–50 to 1370°C
±2°C
T
Copper/Constantan
–454 to 752°F
±3.6°F
–270 to 400°C
±2°C
E
Chromel/Constantan
–58 to 1382°F
±3.6°F
–50 to 750°C
±2°C
B
Pt-30%RH/Pt-6% RH
32 to 3272°F
±5.4°F
0 to 1800°C
±3°C
R
Pt-13%RH/Pt
32 to 3182°F
±3.6°F
0 to 1750°C
±2°C
S
Pt-10%RH/Pt
32 to 3182°F
±3.6°F
0 to 1750°C
±2°C
N
Nicrosil/Nisil
–58 to 2372°F
±3.6°F
–50 to 1300°C
±2°C
L
Iron/Nickel-Copper
–328 to 1652°F
±3.6°F
–200 to 900°C
±2°C
RTD
PT 100 ohms (DIN)
–328 to 752°F
±0.72°F
–200 to 400°C
±0.4°C
RTD
PT 100 ohms (JIS)
–328 to 752°F
±0.72°F
–200 to 400°C
±0.4°C
Linear
Voltage or Current
–1999 to 9999
±0.05%
–1999 to 9999
±0.05%
Line Voltage: 90-264 VAC, 50-60 Hz, 11-26VDC available.
Input: Type: J, K, R, T, B, E, S, N,L thermocouple, PT100
ohm RTD (DIN) 43760/BS1904 (or JIS) and –10 to
60mV (given span).
Power consumption: 10VA, 5W maximum
Accuracy: ±.1%, ± least significant digit.
Maximum Temperature Ranges:
Input
Resolution:
18 bits
Sampling:
5 times/second
Maximum Rating:
-2VDC minimum, 12VDC
maximum (1 minute for mA
input)
Burn-out Current:
200mA