HSP1
High Limit Set Point 1
100.0°C
— Low: HSP.L; High: HSP.H
(212.0°F)
LSP1
Low Limit Set Point 1
0°C
—Low: LSP.L; High: LSP.H
(32°F)
SP2
Set Point 2 Value for Output 1
190.0°C
(194.0°F)
Input Type Selection
—0 J Type T/C
—1 K Type T/C
—2 T Type T/C
—3 E Type T/C
—4 B Type T/C
—5 R Type T/C
—6 S Type T/C
—7 N Type T/C
—8 L Type T/C
—9 PT100 ohms DIN curve
—10 PT100ohms JIS curve
—11 4-20 mA linear current
—12 0~20 mA linear current
—13 0~60 mV linear current
—14 0~1V linear voltage
—15 0~5V linear voltage
—16 1~5V linear voltage
—17 0~10V linear voltage
Process Unit
—0 Degree C unit
—1 Degree F unit
—2 Process Unit
Display Resolution
—0 No decimal point
—1 1 decimal point
1
—2 2 decimal points
—3 3 decimal points
IN.LO
Low Scale Value for Linear Input
—Low: -19999; High: IN.HI
0
IN.HI
High Scale Value for Linear Input
—Low: IN.LO; High: 45536
SHIF
PV Shift (offset) Value
—Low: -200.0°C (360.0°F);
0.0
— High: 200.0°C (350.0°F)
PV Filter Time Constant
—0 0 second
—1 0.2 second
—2 0.5 second
—3 1 second
—4 2 second
Output 1 Function
—2 High limit control
—3 Low limit control
—4 High/Low limit control
O1.HY
Output 1 Hysteresis Value
—Low: 0.1; High: 10.0°C (18.0°F)
HPS.L
Lower Limit of HSP1
—Low: -19999; High: HSP.H
HSP.H
Upper limit of HSP1
—Low: HSP.L; High: 45536
13
Index Description
Default
Code
—Adjusting Range
Setting
LSP.H
Upper Limit of LSP1
0°C
—Low: LSP.L
(32°F)
Output 2 Function
—0 No function
—1 DC power supply output
—2 RS-485 Communication
—
—3 Alarm output
—4 Limit annunciator
—5 Event Input
ADDR
Address Assignment of Digital COMM
—
—Low: 1; High: 255
Band Rate of Digital COMM
—0 0.3 Kbits/s
—1 0.6 Kbits/s
—2 1.2 Kbits/s
—3 2.4 Kbits/s
—4 4.8 Kbits/s
—5 9.6 Kbits/s
5
—6 14.4 Kbits/s
—7 19.2 Kbits/s
—8 28.8 Kbits/s
—9 38.4 Kbits/s
Parity Bit of Digital COMM
PARI
—0 8 bit even parity
—1 8 bit odd parity
0
—2 8 bit none parity
Alarm Function
AL.FN
—6 Process value high alarm
5
—7 Process value low alarm
AL.MD
Alarm Mode
—0 Normal alarm action
0
—1 Latching alarm action
AL.HY
Alarm Hysteresis Value
—Low: 0.1; High: 10°C (18°F)
0.1
AL.FT
Alarm Failure Transfer
—0 Alarm output goes off as unit fails
1
—1 Alarm output goes on as unit fails
Event Input Function
—0 No event function
EIFN
—1 Remote reset for output 1 and
0
output 2, output 1 on, output 2 off
—2 Remote lock for unit
Normal Display Function
DISP
—0 Display process value
0
—1 Display HSP1 or LSP1 value
—2 Display the word SAFE
PV.HI
Historical Maximum Value of PV
—Low: -19999; High: 45536
—
PV.LO
Historical Minimum Value of PV
—
—Low: -19999; High: 45536
Accumulated Time During
T.ABN
Abnormal Condition
—
—Low: 0; High: 6553.5 minutes
INPT
UNIT
RESO
1
(0)
2
FILT
2
OUT1
Index Description
Default
Code
—Adjusting Range
Setting
OUT2
BAUD
–
1000.0°C
(1832.0°F)
Table 5.1 Index Code (Menu) Descriptions:
(Do not disconnect power for at least 12 seconds after changing any control values.
This allows the parameters to be entered into memory.)
NOTE: Further parameter definitions
on pages 14 and 15
—5 5 second
—6 10 second
—7 20 second
—8 30 second
—9 60 second
1
(0)
100.0
0.1