Limit Control
OUT1:
Selects the output 1 function. The available output
1 functions are: High Limit Control, Low Limit Control and
High/Low Limit Control. Refer to page 16 for the limit
control operation.
O1HY: Output 1 hysteresis value. The hysteresis value is
adjusted to a proper value to eliminate the relay
jitter in a noisy environment.
Set Point Range
HSP.L: Lower limit of HSP1.
Hidden if LO is selected for OUT1
HSP.H:Upper limit of HSP1
Hidden if LO is selected for OUT1
LSP.L: Lower limit of LSP1
Hidden if HI is selected for OUT1
LSP.H: Upper limit of LSP1
Hidden if HI is selected for OUT1
HSP.L and HSP.H in set up menu are used to confine the
adjustment range of HSP1. LSP.L and LSP.H are used to
confine the adjustment range of LSP1.
PV Shift
In certain applications it is desirable to shift the indicated
value from its actual value. This can be easily accom-
plished by using the PV shift function.
Cycle the unit to the SHIF parameter by using the scroll
key. The number you adjust here, either positive or nega-
tive, will be added to the actual value. The SHIF function
will alter PV.
SHIF: PV shift (offset) value
Digital Filter
In certain applications the process value is too unstable
to be read. To improve this, a programmable low pass fil-
ter incorporated in the ETR-9040 can be used. This is a
first order filter with a time constant specified by the FILT
parameter which is contained in the set up menu. The
FILT is defaulted to 0.5 seconds before shipping. Adjust
FILT to change the time constant from 0 to 60 seconds. 0
second represents no filter is applied to the input signal.
The filter is characterized by the following diagram.
Figure 5.1
Filter Characteristics