00_200_202_08_01_002-EN | www.ochsner.com 29
Machine-specific engineering and preparation
8.4.2 Heat pumps for single-phase power supply
1 Control box for the heat pump indoor unit
2 Main system distributor
3 Supply to main electrical circuit (compressor)
4 PSU signal contact
5 Supply to control circuit (OTS controller)
6 Supply to electric auxiliary heater
7 Control box for the heat pump outdoor unit
8 External power contactor
8.4.5 Fuse protection
Fuse protection, main
power circuit
AIR FALCON
212 C11A
T200
AIR FALCON
212 C11B
T200
AIR FALCON
212 C11B
T201
Fuse protection
1x B20A 3p
1x B25A 1p
1x B25A 1p
Fuse protection, con-
trol circuit
AIR FALCON
212 C11A
T200
AIR FALCON
212 C11B
T200
AIR FALCON
212 C11B
T201
Fuse protection
1x B13A 1p
1x B13A 1p
1x B13A 1p
Auxiliary heater fuse
protection
AIR FALCON
212 C11A
T200
AIR FALCON
212 C11B
T200
AIR FALCON
212 C11B
T201
Fuse protection
2x B16A 1p
2x B16A 1p
2x B16A 1p
8.4.6 Cables from main distributor to indoor unit
Description
Cores
Min. cable
cross-sec-
tion
Electric auxiliary heater
supply
2x 230 VAC
(L/N/PE)
2.5 mm²
Control circuit supply
1x 230 VAC
(L/N/PE)
1.5 mm²
Power contactor
2x 230 VAC
(L/N)
1.5 mm²
LAN connection line
Description
LAN cable
Type
Min. CAT 5
Connections
RJ45 connector
8.4.7 Cables to sensors and actuators
Description
Cores
Min. cable
cross-sec-
tion
Supply to pumps and servo-
motors
L/N/PE
1.0 mm²
Sensor leads
(system temperature sensors)
2x
(shielding recommend-
ed)
1.0 mm²
Bus cables
Example:
Y(ST)Y 2x2x0.8
(shielded cable design
and twisted cable
pairs)
0.8 mm²
8.4.8 Lines to the outdoor unit
Description
Type
Cores
Min. cable
cross-sec-
tion
Bus cable
-
Y(ST)Y
2x2x0.8
BK/RD/WH/
YE
0.8 mm²
Supply to main
power circuit
(compressor)
AIR FALCON
212 C11A
3x 400 VAC
(L1/L2/L3/N/
PE)
4 mm²
AIR FALCON
212 C11B
1x 230 VAC
(L/N/PE)
4 mm²
Material damage
Protect the cables to the outdoor unit against UV
radiation. Use a UV-resistant cable or a cable in a
UV-resistant hose.
Material damage
Protect the cables to the outdoor unit against dam-
age from rodents.
8.4.9 Temperature sensor
Note
The maximum line length for sensor leads is 50 m.
Note
Sensor leads must be routed separately from 230 V
and 400 V cables. If a minimum distance of 20 cm
cannot be maintained, then shielded cables should
be used. The shielding should be connected to the
earth rail of the heat pump.
Outdoor temperature (T-AU):
»
Fit the outdoor temperature sensor to the outside wall
of the building (on the north-west side) at a height of
approx. 2.5 m. Make sure that the outdoor tempera-
ture sensor is not exposed to direct sunlight or wind,
as this will impair the control characteristics.
Содержание AIR FALCON 212 C11A T200
Страница 2: ...2 www ochsner com PIA 982043 AIR FALCON T200 ih EN...
Страница 7: ...PIA 982043 AIR FALCON T200 sh EN www ochsner com 7 Safety...
Страница 9: ...00_400_200_202_01_split_Funktionsweise EN www ochsner com 9 How split systems work...
Страница 13: ...00_200_202_08_02_002 EN www ochsner com 13 Device description...
Страница 31: ...00_200_202_08_01_002 EN www ochsner com 31...
Страница 47: ...PIA 982043 AIR FALCON T200 in EN www ochsner com 47...
Страница 51: ...00_400_01_01 EN www ochsner com 51...
Страница 64: ...64 www ochsner com PIA 982043 AIR FALCON T200 td EN Dimensions and connections 20 2 1 Drainage plug...
Страница 65: ...PIA 982043 AIR FALCON T200 td EN www ochsner com 65...
Страница 67: ...PIA_982043_AIR_FALCON_T200_EN06 1 www ochsner com 67...