00_200_202_08_01_002-EN | www.ochsner.com 27
Machine-specific engineering and preparation
8.3 Indoor unit
8.3.1 Minimum clearances
A
B
C
D
E
≥ 800 mm
≥ 100 mm
≥ 500 mm
≥ 100 mm
≥ 400 mm
≥ 500 mm
≥ 100 mm
8.4.4
Minimum area of clear floor space in the
installation room
Each refrigerant requires a minimum area of clear floor
space in the installation room. No other objects are allowed
to stand in this area. Objects may be hung in this space if
they are installed at a height of at least 0.6 m.
(E.g.: buffer
tank, wall shelf)
Connection line length
Min. clear floor space
[m]
[m
2
]
5
16.7
6
16.7
Connection line length
Min. clear floor space
[m]
[m
2
]
7
16.7
8
16.7
9
17.2
10
17.8
11
18.5
12
19.2
13
19.9
14
20.6
15
21.3
16
22.1
17
22.8
18
23.6
19
24.4
20
25.1
Note
If the installation area is too small, this can be en-
larged by creating a network of rooms (e.g. door
gap).
WARNING
Do not block door gaps and ventilation openings
used to enlarge the space.
8.4 Preparing the electrical connections
WARNING: Electrocution
All electrical connection and installation work must
be carried out according to the applicable national
and regional regulations.
WARNING: Electrocution
Before commencing electrical connection and
installation work, the heat pump system must be
isolated from the power supply.
WARNING: Electrocution
Work on electrical connections and installation may
only be conducted by qualified contractors.
Material damage
This appliance contains frequency converters
(e.g. EC circulation pumps, EC fan motors). Leak-
age currents may arise in normal operation. In the
event of faults, these components may cause DC
fault currents. An incorrectly selected RCD may trip
during normal operation or, in the event of a fault,
may not trip at all or only trip after a delay.
»
Make sure that the power supply for this
appliance is separate from the domestic in-
stallation.
»
Install a type B, AC/DC-sensitive RCD.
Содержание AIR FALCON 212 C11A T200
Страница 2: ...2 www ochsner com PIA 982043 AIR FALCON T200 ih EN...
Страница 7: ...PIA 982043 AIR FALCON T200 sh EN www ochsner com 7 Safety...
Страница 9: ...00_400_200_202_01_split_Funktionsweise EN www ochsner com 9 How split systems work...
Страница 13: ...00_200_202_08_02_002 EN www ochsner com 13 Device description...
Страница 31: ...00_200_202_08_01_002 EN www ochsner com 31...
Страница 47: ...PIA 982043 AIR FALCON T200 in EN www ochsner com 47...
Страница 51: ...00_400_01_01 EN www ochsner com 51...
Страница 64: ...64 www ochsner com PIA 982043 AIR FALCON T200 td EN Dimensions and connections 20 2 1 Drainage plug...
Страница 65: ...PIA 982043 AIR FALCON T200 td EN www ochsner com 65...
Страница 67: ...PIA_982043_AIR_FALCON_T200_EN06 1 www ochsner com 67...