DIAM3100©2012 AUGIER SA.
IV-49
IV.3.2 FAULT DIAGNOSIS
See paragraph I.5.3 for a description of the following protections.
IV.3.2.1 LV power fault:
Symptom
Fault
Action
The CCR has stopped
The message:
“
ALARM : Bad supply
”
is displayed
LV power fault
Check the voltage level of the LV
power supply
Check parameter settings in the
“
Configuration
” menu
IV.3.2.2
“Open Circuit” fault:
Symptom
Fault
Action
The CCR has stopped
The message:
“
ALARM: I << Open Cir
.
”
is displayed
Lighting loop open
Measure the continuity of the loop
(on the transformer primaries and
secondaries)
Output current < 1.0A for more than
500 ms
Measure the output current value
Large load increase on the loop
caused by circuit switching
Fibre optic cables disconnected or
faulty
Check the state of the fibre optic
cables between the regulation board
and the thyristor control boards
Measuring board to motherboard link
faulty
Check state of the ribbon cable
between
measuring
board
and
motherboard
Thyristor trigger-gates faulty
Measure the state of the thyristors
Protection detection level setting on
motherboard
Check setting of the level in the
menu “
Alarms and warnings
” then
“
Open circuit
”
Thyristors faulty in open circuit
Measure the state of the thyristors
Содержание AUGIER energy DIAM3100 Series
Страница 2: ...DIAM3100 2012 AUGIER SA I 2...
Страница 6: ...DIAM3100 2012 AUGIER SA I 6...
Страница 13: ...DIAM3100 2012 AUGIER SA I 13 I 2 4 DIMENSIONS...
Страница 14: ...DIAM3100 2012 AUGIER SA I 14 Stacked CCRs...
Страница 28: ...DIAM3100 2012 AUGIER SA I 28...
Страница 56: ...DIAM3100 2012 AUGIER SA V 56 V APPENDIX A DIAGRAM...