DIAM3100©2012 AUGIER SA.
II-39
II.2.2.1.3 Wiring remote control voltage configuration
The DIAM CCR can be remotely controlled either by an external voltage (20 to 60 VDC positive or
negative), or by “free potential” contacts (internal power supply 30VDC from the CCR). This choice is made by
the values at address 70 in the Jbus table.
CONTROL INPUTS CONFIGURATION
Inputs configuration
Fig
Jbus address
B7 B6 B5 B4 B3 B2 B1 B0
External v20V to +60V-- to
control the inputs
1
70
X
0
X
X
X
X
0
0
External voltage -20V to -60V-- to
control the inputs
2
70
X
1
X
X
X
X
0
0
Contacts to control the inputs.
24V-- internal voltage
3
70
X
0
X
X
X
X
0
1