II-42
II.3.2 PARAMETER MODIFICATION
Preferably, and according to the CCR, the parameters are
pre-set in the factory as ordered
, so it is not
necessary to reconfigure them during device installation and commissioning.
II.3.2.1 Preferred configuration values:
The preferred configuration (if no precision on orders, or in case of new mother board) is as follow :
•
Setting
I B0 = 1.50 A
I B1 = 2.80 A
I B2 = 3.40 A
I B3 = 4.10 A
I B4 = 5.20 A
I B5 = 6.60 A
Brightness number = 6
Maxi current = Setting value + 100mA
Mini current = Setting value - 100mA
•
Protection
Earth fault level 1 = 1M
(if option present)
Earth fault level 2 = 100K
(if option present)
Restarts number = 1
Over-current level 1 = 6.80 A (+ 3%)
Disable time = 2.50 s
Over-current level 2 = 6.93 A (+ 5%)
Disable time = 1s
Over-current level 3 = 8.25A (+ 25%)
Disable time = 200 ms
Open circuit current = 1.00A
Disable time = 600 ms
•
Burnt lamps
Burnt lamps level 1 = 5 (if option present)
Burnt lamps level 2 = 10 (if option present)
Calibration cancelled.
•
Wig wag
Cycle time = 2.5s
On time = 1.7s
•
USB link
Slave Id = 1
Baud Rate = 38400
•
Jbus RS485 link
Slave Id = 1
Baud Rate = 9600