DIAM3100©2012 AUGIER SA.
I-19
I.4.3 LOCAL INFORMATION FEEDBACK
Alphanumeric display:
•
The display shows the RMS current flowing in the loop and the selected brightness (preferably).
In the “
Monitoring”
menu, the following information is shown:
•
Uo: RMS output voltage in Vrms
•
Po: RMS output power in KVA
•
Ui: Mains power supply voltage in Vrms
•
Load plate tap value from 0 to 100% (0 to 4/4 by increments of 1/4)
•
If option “LFD” is activated: Number of burnt lamps
•
If option “Time meters” is activated: The operating time (powered on and for each brightness) in Hours
Warning:
WARNING is an indicative message, which does not change the regulation function, and supply function in
connection with the load. (Except for mains warning)
If any warning have been detected, the following message(s) can be shown on the display:
•
With the LFD
option (“Burnt lamps”) :
“Level 1 Burnt lamps” (The current number of burnt lamps is greater than level 1)
“Level 2 Burnt lamps” (The current number of burnt lamps is greater than level 2)
•
Mains power supply outside limits (Input voltage lower or greater than +/-10%)
•
Regulation outside limits (as “error regulation” programmed values)
Fault:
ALARM represents a major fault of the CCR or due to an external event, which have stopped the CCR (in order
to protect itself or the lighting loop).
In case of fault or damage, the display shows that the CCR stopped and that one or more faults have been
detected. The following message(s) are shown on the display :
•
Overcurrent Level 1 (after a trial to restart, the CCR cannot contain the output current which had reach
the 1
st
level as programmed)
•
Overcurrent Level 2 (ditto, for 2
nd
level)
•
Overcurrent Level 3 (ditto, for 3
rd
level)
•
Peak Overcurrent (ditto, for a 4
th
level, not configurable)
•
Open circuit (the CCR detected an output current lower and during a greater time than the programmed
parameters)
In order to re-start (after having fixed the fault), cancel the ALARM pressing the RESET key.
I.4.4 REMOTE INFORMATION FEEDBACK
•
RS485/RS422 Jbus link is fitted in standard.
•
One supplementary RS485/RS422 Jbus link can be provided in option.
•
One or two Insulated ETHERNET link can be provided in option.
•
Multiwire remote control (SOURIAU CONNECTORS) can be provided in option.
See II.2.for more details.
See the JBUS table in the appendix b: jbus table, for more details.
Содержание AUGIER energy DIAM3100 Series
Страница 2: ...DIAM3100 2012 AUGIER SA I 2...
Страница 6: ...DIAM3100 2012 AUGIER SA I 6...
Страница 13: ...DIAM3100 2012 AUGIER SA I 13 I 2 4 DIMENSIONS...
Страница 14: ...DIAM3100 2012 AUGIER SA I 14 Stacked CCRs...
Страница 28: ...DIAM3100 2012 AUGIER SA I 28...
Страница 56: ...DIAM3100 2012 AUGIER SA V 56 V APPENDIX A DIAGRAM...