nVent RAYCHEM Elexant 4010i/4020i User Manual
RAYCHEM-AR-H60624-40X0iOpsManual-EN-1905
nVent.com
|
96
8. APPENDIX A
LIST OF ABBREVIATIONS
E – Enabled
D – Disabled
L – Latching
NL – Non-Latching
Table 34 – List of Abbreviations
PROFILES - DEFAULT SETTINGS
Configuration
Page
Description
Default Profile
Process Profile
Ambient Profile
Default
State
Default
Setpoint
/Value
Default State Default
Setpoint
/Value
Default
State
Default
Setpoint
/Value
Control
Temp
Control Setpoint
20
20
5
Fail Mode
OFF
OFF
OFF
Aggregation Mode
LOWEST
LOWEST
LOWEST
High Temp Alarm
D,NL
100
D,NL
100
D,NL
80
High Temp Filter
0
0
300
Low Temp Alarm
E,NL
5
E,NL
5
E,NL
-40
Low Temp Filter
0
0
0
0
300
Failure
E,L
E,L
E,L
Control
Mode
Control Mode
On/Off
On/Off
PASC
Output Type
Contactor
Contactor
Contactor
Dead band
3 C
3 C
3 C
Min. Ambient
N/A
N/A
-40 C
Min. Pipe Size
N/A
N/A
0.5”(12.5mm)
Power Adjust
N/A
N/A
100%
Load
Shedding
Load Shedding
D
D
D
FailSafe
D
D
D
Timeout
60 Sec
60 Sec
60 Sec
Misc
Cycle Count
E
100000
E
100000
E
100000
Heater on Time
E
100000
E
100000
E
100000
Autocycle
E
8
E
8
E
8
Alarm Mode
Normal
Normal
Normal
Digital Input
Not used
Not used
Not used
Temperature
Sensor (x)
TS1 Type
RTD-
PT100
RTD-PT100
RTD-PT100
TS1 Mode
Control
Control
Control
TS1 High Temp Alarm D,NL
100
D,NL
100
D,NL
80
TS1 High Temp Filter
0
0
300
TS1 Low Temp Alarm E,NL
5
E,NL
5
E,NL
-40
TS1 Low Temp Filter
0
0
300
TS1 Failure
E,L
E,L
E,L
TS2 Type
None
None
None
TS2 Mode
Monitor
Monitor
Monitor