nVent RAYCHEM Elexant 4010i/4020i User Manual
RAYCHEM-AR-H60624-40X0iOpsManual-EN-1905
nVent.com
|
14
Figure 8 - RS-485 IN
2.6.5 RS-485 OUT
Wiring for the RS-485 data connections may be terminated directly on the module TB-2 terminal blocks
as shown or on panel mounted terminal blocks. Shielded cables should not be terminated on terminals
of TB2. Terminate RS-485 cable shields on panel mounted field terminals as shown in the figure below.
Note
•
Install a 120 Ohm termination resistor as shown if this is the last device in the communication bus.
Figure 9 - RS-485 Out
Содержание RAYCHEM Elexant 4010i
Страница 1: ...RAYCHEM AR H60624 40X0iOpsManual EN 1905 nVent com 1 nVent RAYCHEM Elexant 4010i 4020i User Manual ...
Страница 99: ...RAYCHEM AR H60624 40X0iOpsManual EN 1905 nVent com 99 ...
Страница 100: ...nVent RAYCHEM Elexant 4010i 4020i User Manual RAYCHEM AR H60624 40X0iOpsManual EN 1905 nVent com 100 ...