Procedure:
Touch the field for which the value needs to be modified.
5.6.7.1 Controller Tag
Figure 82 - Controller Tag Entry
Purpose:
This parameter is a 40-character tag assigned to the controller or EHT circuit for easy identification.
Range:
Alpha-numeric characters.
Default:
Elexant 4010i/4020i-xxxxxx.
5.6.7.2 Autocycle
Figure 83 - Autocycle Settings
Range:
1 to 750 Hours
Purpose:
The Autocycle interval is user programmable and periodically energizes the circuit for 30 seconds to
detect any alarm conditions. Circuit alarms are be generated at the time of autocycle instead of when
heat is required. This feature eliminates the need for a preventive maintenance program as these tests
are performed at regular intervals by the controller.
Default:
8 Hours
5.6.7.3 Alarm Mode
Purpose:
The Alarm Mode defines the behavior of the alarm output.
1. Normal:
Figure 84 - Alarm Mode Normal Setting
The alarm output is active when an alarm condition exists, inactive when there is no alarm condition.
2. Toggle:
Figure 85 - Toggle Time Period Settings
The alarm output is active when an alarm condition exists and the alarm relay changes state for a period
of time (the toggle time) whenever a new alarm is generated. The user may define the toggle time by
entering the desired duration.