nVent RAYCHEM Elexant 4010i/4020i User Manual
RAYCHEM-AR-H60624-40X0iOpsManual-EN-1905
nVent.com
|
28
3.2.1.7 Lead Resistance
Purpose:
This parameter is applicable only to 2-wire 100-Ohm Nickel Iron
and 2-wire 100-Ohm Nickel
RTDs. Since a 2-wire RTD has no compensation for lead resistance, entering a value will allow the
temperature reading to be corrected to compensate for this lead resistance.
Range:
0 to 20 Ohms.
Default:
0 Ohms.
3.2.1.8 High/Low Temperature Alarm Settings
Note: see Section 3.5.2 for more details on alarm functionality.
a. Enable
Purpose:
This parameter is used to enable or disable the activation of the High/Low Alarms.
High Temperature Alarm Defaults:
TS1: Disabled
TS2: Disabled
TS3: Disabled
Low Temperature Alarm Defaults:
TS1: Enabled
TS2: Disabled
TS3: Disabled
b. Latch
Purpose:
This parameter is used to configure the behavior of the High/Low Alarm conditions. Disabling
the Latch function will allow the alarm to self-clear once the alarm condition has resolved. Enabling
latching will keep the alarm active until it is reset by the user or the controller is reset (by a cycling the
power on/off for example).
High Temperature Alarm Latch Defaults:
TS1: Disabled
TS2: Disabled
TS3: Disabled
Low Temperature Alarm Latch Defaults:
TS1: Disabled
TS2: Disabled
TS3: Disabled
c. Setpoint
Purpose:
This parameter is used to enter a temperature value at which the controller sets the High/Low
Alarm indicator.
Range:
-200°C to 700°C.
Default High Alarm Setpoint: 100°C.
Default Low Alarm Setpoint: 5°C.
d. Filter
Purpose:
Filter is the minimum amount of time that a High/Low Alarm condition must exist before the
controller sets the High/Low Alarm indicator.
Range:
0 to 59940 seconds.
Default:
0 Seconds