5.13.1 Safety Limiter Setup
Touch the corresponding
Enable
check box to turn on/off the corresponding Alarm indication and touch
the corresponding
Latch
check box to select a latching or a non-latching alarm type. When latching is
selected, then the alarm will need to be manually reset each time the corresponding alarm occurs.
Figure 141 - Safety Limiter Alarm Setup
5.13.1.1 Safety Limiter Status
Purpose:
This field shows the status of the Safety Limiter Output.
Values:
OK, Tripped.
Figure 142 - Safety Limiter Status – OK
Figure 143 - Safety Limiter Status – Tripped
5.13.1.2 Safety Limiter Temperature
Figure 144 - Actual Temperature Reading
Purpose:
This field shows the temperature measured by the Limiter RTD. If this value exceeds the Safety
Limiter set point, the Safety Limiter will trip open. In the case where the Safety Limiter has tripped, a
manual intervention is required to reset the trip condition. This is only possible once all process
conditions have returned to a safe state.
5.13.1.3 Safety Limiter Temperature Setpoint
Figure 145 - Safety Limiter Temperature Setpoint
Purpose:
This field displays the Safety Limiter temperature setpoint value.The value should be chosen
in accordance with the Temperature Class of the area in which the heating application is installed or the
maximum surface temperature allowed for the heating device, whichever is less.
Default:
50°C
Range:
50 to 600°C